229
APPENDIX F — BACNET COMMUNICATION OPTION (cont)
NETWORK POINTS LIST (cont)
See legend on page 233.
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Compressor B1 Run Hours HR_B1 R hr 0 - 999999.9 AV:32 hr_b1_1
Compressor B1 Starts CY_B1 R 0 - 999999 AV:33 cy_b1_1
Compressor B1 Strikes CMPB1STR R 0 - 3 AV:34 cmpb1str_1
Compressor B2 Relay CMPB2 R 0 - 1 BV:19 cmpb2_1
Compressor B2 Run Hours HR_B2 R hr 0 - 999999.9 AV:36 hr_b2_1
Compressor B2 Starts CY_B2 R 0 - 999999 AV:37 cy_b2_1
Compressor B2 Strikes CMPB2STR R 0 - 3 AV:38 cmpb2str_1
Compressor B3 Relay CMPB3 R 0 - 1 BV:14 cmpb3_1
Compressor B3 Run Hours HR_B3 R hr 0 - 999999.9 AV:27 hr_b3_1
Compressor B3 Starts CY_B3 R 0 - 999999 AV:31 cy_b3_1
Compressor B3 Strikes CMPB3STR R 0 - 3 AV:35 cmpb3str_1
Compressor B4 Run Hours HR_B4 R hr AV:126 hr_b4_1
Compressor B4 Starts CY_B4 R AV:127 cy_b4_1
Compressor B4 Strikes CMPB4STR R AV:128 cmpb4str_1
Compressor Lockout Temp OATLCOMP R/W °F 40 -20 - 55 AV:40 oatlcomp_1
Condenser EXV Position COND_EXV R % 0 - 100 AV:39 cond_exv_1
Condenser Fan Output 1 CONDFAN1 R 0 - 1 BV:15 condfan1_1
Condenser Fan Output 2 CONDFAN2 R 0 - 1 BV:21 condfan2_1
Condenser Fan Output 3 CONDFAN3 R 0 - 1 BV:23 condfan3_1
Condenser Fan Output 4 CONDFAN4 R 0 - 1 BV:24 condfan4_1
Condenser Fan Output 5 CONDFAN5 R 0 - 1 BV:49 condfan5_1
Controlling Return Air Temp RETURN_T R/W dF -40 - 240 AV:1030 re_temp_1
Controlling Space Temp SPACE_T R/W dF -40 - 240 AV:2007 space_temp_1
Cool Mode Not In Effect? COOL_OFF R 0 - 1 BV:20 cool_off_1
Cooling Control Point COOLCPNT R dF -20 - 140 AV:1024 cool_ctrl_point_1
Cooling Occupied Setpoint OCSP R/W °F 40 - 99 AV:3001 occ_cl_stpt_1
Cooling Unoccupied Setpoint UCSP W °F 40 - 110 AV:3003 unocc_cl_stpt_1
Ctl.Temp RAT,SPT or ZONE CTRLTEMP R °F 0 - 100 AV:43 ctrltemp_1
Current Running Capacity (Heat) HTSG_CAP R % 0 - 100 AV:44 htsg_cap_1
Currently Occupied MODEOCCP R 0 - 1 BV:37 modeoccp_1
Currently Occupied ? MODE_OCC R 0 - 1 BV:39 mode_occ_1
Current Running Capacity CAPTOTAL R % 0 - 100 AV:1023 cool_capacity_1
DBC - OAT Lockout? DBC_STAT R 0 - 1 BV:25 dbc_stat_1
DCV Resetting Min Pos MODEADCV R 0 - 1 BV:26 modeadcv_1
DDBC- OAT > RAT Lockout? DDBCSTAT R 0 - 1 BV:27 ddbcstat_1
DEC - Diff.Enth.Lockout? DEC_STAT R 0 - 1 BV:28 dec_stat_1
Dehumid. Disabled Econ.? DHDISABL R 0 - 1 BV:29 dhdisabl_1
Dehumidify Cool Setpoint DHCOOLSP R/W °F 40 - 55 AV:49 dhcoolsp_1
Dehumidify Input DHDISCIN W 0 - 1 BV:30 dhdiscin_1
Dehumidify RH Setpoint DHRELHSP R/W % 55 10 - 90 AV:50 dhrelhsp_1
Demand Limit In Effect MODEDMLT R 0 - 1 BV:31 modedmlt_1
Demand Limit Sw.1 Setpt. DLSWSP1 R/W % 80 0 - 100 AV:53 dlswsp1_1
Demand Limit Sw.2 Setpt. DLSWSP2 R/W % 50 0 - 100 AV:54 dlswsp2_1
Demand Limit Switch 1
DMD_SW1 W 0 - 1 BV:1006 dmd_sw1_1
Demand Limit Switch 2 DMD_SW2 W 0 - 1 BV:1007 dmd_sw2_1
DEW - OA Dewpt.Lockout? DEW_STAT R 0 - 1 BV:32 dew_stat_1
Diff.Air Quality in PPM DAQ R 0 - 5000 AV:56 daq_1
Dmd Level Low Cool ON DMDLCON R/W ^F 1.5 0 - 2 AV:63 dmdlcon_1
Dmd Level Low Heat ON DMDLHON R/W ^F 1.5 0 - 2 AV:64 dmdlhon_1
Dmd Level Map Select M684 W BV:2 m684_1
Dmd Level(-) Low Cool OFF DMDLCOFF R/W ^F 1 0.5 - 2 AV:59 dmdlcoff_1
Dmd Level(-) Low Heat OFF DMDLHOFF R/W ^F 1 0.5 - 2 AV:60 dmdlhoff_1
Dmd Level(+) Hi Cool ON DMDHCON R/W ^F 0.5 0.5 - 20 AV:61 dmdhcon_1
Dmd Level(+) Hi Heat ON DMDHHON R/W ^F 0.5 0.5 - 20 AV:62 dmdhhon_1
Econ 1 Out Act.Curr.Pos. ECON1POS R % AV:1028 econ1_pos_1
Econ 2 Out Act.Curr.Pos. ECON2POS R % AV:130 econ2_pos_1
Econ 3 Out Act.Curr.Pos. ECON3POS R % AV:136 econ3_pos_1
Econ Act. Unavailable? ECONUNAV R 0 - 1 BV:34 econunav_1
Econ disable in DH mode? DHECDISA W Yes 0 - 1 BV:35 dhecdisa_1
Econ Recovery Hold Off? ECONHELD R 0 - 1 BV:42 econheld_1
Econ1 Act. Unavailable? ECON1UNAV R BV:51 econ1unav_1
Econ1Out Act. Cmd Pos ECONOCMD R/W % 0 - 100 AV:67 econocmd_1
Econ2 Act. Unavailable? ECON2UNAV R BV:57 econ2unav_1
Econ2 Ret Cmd Position ECN2CPOS R/W % 0 - 100 AV:41 ecn2cpos_1