230
APPENDIX F — BACNET COMMUNICATION OPTION (cont)
NETWORK POINTS LIST (cont)
See legend on page 233.
POINT DESCRIPTION CCN POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Econ3 Act. Unavailable? ECON3UNAV R BV60 econ3unav_1
Econ3 Ret Cmd Position ECN3CPOS R/W % 0 - 100 AV:129 ecn3cpos_1
Econo Current Min. CFM ECMINCFM R CFM 0 - 20000 AV:42 ecmincfm_1
Econo Current Min. Pos. ECMINPOS R % 0 - 100 AV:45 ecminpos_1
Economizer Active? ECACTIVE R 0 - 1 BV:36 ecactive_1
Economizer Control Point ECONCPNT R °F 0 - 180 AV:68 econpnt_1
Economizer Forced ? ECONFORC R 0 - 1 BV:38 econforc_1
Economizer Max.Position ECONOMAX R/W % 98 0 - 100 AV:70 economax_1
Economizer Min.Flow OACFMMAX R/W CFM 2000 0 - 20000 AV:46 oacfmmax_1
Economizer Min.Position ECONOMIN W % 5 0 - 100 AV:4005 econ_min_1
EDT Sensor Bad ? EDT_STAT R 0 - 1 BV:44 edt_stat_1
Element Comm Status R BV:2999 element_stat_1
Element Communications Alarm R BV:105 comm_lost_alm_1
Emergency Stop EMSTOP W 0 - 1 BV:45 emstop_1
Enth. Switch Read High ? ENTH W 0 - 1 BV:40 enth_1
Equipment Alarm R BV:127 element_alarm_1
Evacuation Input EVAC W 0 - 1 BV:1060 smk_evac_1
Evaporator Discharge Tmp EDT R °F AV:76 edt_1
Exhaust Air CFM EACFM R cfm AV:140 eacfm_1
Exhaust Fan VFD Speed EFAN_VFD R % 0 - 100 AV:2075 ef_vfd_output_1
Fan Fail Shuts Down Unit SFS_SHUT W No 0 - 1 BV:50 sfs_shut_1
Fan Mode FAN_MODE R/W 1 0 - 1 AV:77 fan_mode_1
Fan request from IGC IGCFAN R 0 - 1 BV:11 igcfan_1
Fan Track Control D.CFM DELTACFM R CFM AV:47 deltacfm_1
Fan Track Internal RAM DCFM_RAM R/W CFM 0 -20000 - 20000 AV:48 dcfm_ram_1
Fan Track Max Clamp DCFM_MAX R/W CFM 4000 0 - 20000 AV:51 dcfm_max_1
Fan Track Max Correction DCFM_ADJ R/W CFM 1000 0 - 20000 AV:52 dcfm_adj_1
Filter Status Input FLTS W 0 - 1 BV:1052 filter_status_1
Fire Shut Down Emergency Mode A404 R BV:114 a404_1
Fire Shutdown Input FSD W 0 - 1 BV:1005 firedown_status_1
Freeze Status Switch FRZ W 0 - 1 BV:41 frz_1
Heat Interlock Relay HIR W 0 - 1 BV:1026 heat_interlock_relay_1
Heat Reclaim Relay HTRCLRLY R BV:62 htrclrly_1
Heat Relay 1 HS1 R 0 - 1 BV:52 hs1_1
Heat Relay 10 HS10 R BV:71 hs10_1
Heat Relay 2 HS2 R 0 - 1 BV:53 hs2_1
Heat Relay 7 HS7 R BV:64 hs7_1
Heat Relay 8 HS8 R BV:65 hs8_1
Heat Relay 9 HS9 R BV:66 hs9_1
Heat-Cool Setpoint Gap HCSP_GAP R/W °^F 2 - 10 AV:83 hcsp_gap_1
Heating Control Point HEATCPNT R -10 - 140 AV:1025 heat_ctrl_point_1
Heating Occupied Setpoint OHSP R/W °F 40 - 99 AV:3002 occ_ht_stpt_1
Heating Supply Air Setpt SASPHEAT R/W dF 85 80 - 120 AV:85 saspheat_1
Heating Unoccupied Setpoint UHSP R/W °F 40 - 99 AV:3004 unocc_ht_stpt_1
Hi Limit Switch Tmp Mode
LIMTMODE R 0 - 1 BV:55 limtmode_1
High OAT Lockout Temp OAT_LOCK R/W dF 60 -40 - 120 AV:9008 econ_oat_lockout_1
Ht.Coil Command Position HTCLCPOS R % 0 - 100 AV:55 htclcpos_1
Humidifier Relay HUMIDRLY R 0 - 1 BV:46 humidrly_1
HumidiMizer 3-way Valve HUM3WVAL R 0 - 1 BV:47 hum3wval_1
HumidiMizer Capacity HMZRCAPC R % 0 - 100 AV:57 hmzrcapc_1
HVAC Mode Numerical Form MODEHVAC R 0 - 40 AV:1022 hvac_mode_1
IAQ - Discrete Input IAQIN W 0 - 1 BV:1050 iaq_status_1
IAQ - PPM Indoor CO2 IAQ W 0 - 5000 AV:1009 iaq_1
IAQ Demand Vent Min.Flow OACFMMIN R/W CFM 0 0 - 20000 AV:58 oacfmmin_1
IAQ Pre-Occ Purge Active MODEIQPG R 0 - 1 BV:56 modeiqpg_1
IAQ Purge Duration IAQPTIME R/W min 15 5 - 60 AV:98 iaqptime_1
IAQ Purge OAT Lockout IAQPNTLO R/W °F 50 35 - 70 AV:101 iaqpntlo_1
Indoor Air CO2 LINK_IAQ R AV:2607 link_iaq_1
LAT Cutoff Mode LATCMODE R 0 - 1 BV:58 latcmode_1
Leaving Air Temperature LAT R dF -40 - 240 AV:1027 lvg_air_temeprature_1
Linkage Collector LINK_COLLECTOR R COLLECTOR link_collector_1
Linkage Config Error/Data Invalid A_LINK_CONFIG_ERROR R BV:2604 a_link_config_error_1
Linkage Max Damper Position LINK_MAX_DMPR R/W AV:2611 link_max_dmpr_1
Linkage Optimal Start A_LINK_OPT_START R BV:2603 a_link_opt_start_1
Local Machine Disable UNITSTOP W 0 - 1 BV:59 unitstop_1