APPENDIX F — BACNET COMMUNICATION OPTION (cont)
NETWORK POINTS LIST (cont)
See legend on page 233.
POINT DESCRIPTION CCN POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Local Schedule SCHEDULE R BV:5 schedule_1
Local Schedule/Override Time Remaining SCHEDULE_OVERRIDE_
TIME_REMAINING
R AV:155 schedule_override_time_
remaining_1
Low Temp Cap Override LOW_TEMP R 0 - 1 BV:61 low_temp_1
Main Filter Delta Press MF_DP R AV:141 mf_dp_1
Main Filter Status MF_STAT R % AV:142 mf_stat_1
Mech Cooling Locked Out MODELOCK R 0 - 1 BV:63 modelock_1
Mixed Air Relative Humidity MARH R/W % 0 - 100 AV:145 marh_1
Mixed Air Temperature MAT R dF AV:1500 ma_temp_1
Modulating Gas Capacity HTMG_CAP R % 0 - 100 AV:65 htmg_cap_1
MtrMaster A Commanded % MM_A_VFD R % AV:146 mm_a_vfd_output_1
MtrMaster B Commanded % MM_B_VFD R % AV:147 mm_b_vfd_output_1
OAEC- OA Enth Lockout? OAECSTAT R 0 - 1 BV:67 oaecstat_1
OAQ - PPM Outdoor CO2 OAQ R/W 0 - 5000 AV:113 oaq_1
OAQ Lockout In Effect ? OAQLOCKD R 0 - 1 BV:68 oaqlockd_1
OAQ Lockout Value OAQLOCK R/W 0 0 - 2000 AV:112 oaqlock_1
OAT Sensor Bad ? OAT_STAT R 0 - 1 BV:69 oat_stat_1
Occupancy Status A_LINK_OCC_STATUS R BV:2602 a_link_occ_status
Occupied Cool Mode End OCCL_END R °F 0 - 100 AV:114 occl_end_1
Occupied Cool Mode Start OCCLSTRT R °F 0 - 100 AV:115 occlstrt_1
Occupied Heat Mode End OCHT_END R °F 0 - 100 AV:116 ocht_end_1
Occupied Heat Mode Start OCHTSTRT R °F 0 - 100 AV:117 ochtstrt_1
Occupied Heating Enabled HTOCCENA W No 0 - 1 BV:70 htoccena_1
Occupied? OCCUPIED W 0 - 1 BV:2008 occ_status_1
Outside Air CFM OACFM R CFM 0 - 50000 AV:66 oacfm_1
Outside Air Humidity Ratio OA_HUMR R AV:118 oa_humr_1
Outside Air Relative Humidity OARH R/W % 0 - 100 AV:119 oarh_1
Outside Air Temperature OAT W dF -40 - 240 AV:1003 oat_1
Override Time Limit OTL R/W hr 1 0 - 4 AV:120 otl_1
Plenum Press.Safety Sw. PPS W 0 - 1 BV:48 pps_1
Post Filter Delta Press PF_DP R AV:148 pf_dp_1
Post Filter Status Input PFLTS_STATUS RW 0 - 1 BV:72 pflts_status_1
Post Filter Status PF_STAT R % 0 - 100 AV:149 pf_stat_1
Power Exhaust Bypass Input PEBYIN R BV:73 pebyin_1
Power Exhaust Bypass Relay PEBYRLY R BV:74 pebyrly_1
Power Fault Input PWRFAULT R BV:80 pwrfault_1
Pressurization Input PRES W 0 - 1 BV:1061 smk_press_1
Pull Down Cap Override PULLDOWN R 0 - 1 BV:75 pulldown_1
Push Button Override PB_ENABLE R/W BV:4 pb_enable_1
Relay 3 W1 Gas Valve 2 HS3 R 0 - 1 BV:76 hs3_1
Relay 4 W2 Gas Valve 2 HS4 R 0 - 1 BV:77 hs4_1
Relay 5 W1 Gas Valve 3 HS5 R 0 - 1 BV:78 hs5_1
Relay 6 W2 Gas Valve 3 HS6 R 0 - 1 BV:79 hs6_1
Remote Alarm/Aux Relay ALRM W 0 - 1 BV:2014 aux_relay_1
Remote Input State RMTIN W 0 - 1 BV:81 rmtin_1
Requested Heat Stage HT_STAGE R 0 - 20 AV:2003 heat_run_1
Reset Limit LIMT R/W ^F 10 0 - 20 AV:131 limt_1
Reset Ratio RTIO R/W 3 0 - 10 AV:132 rtio_1
Return Air CFM RACFM R CFM 0 - 50000 AV:69 racfm_1
Return Air Enthalpy RAE R AV:133 rae_1
Return Air Relative Humidity RARH R/W % 0 - 100 AV:134 rarh_1
Return Air Temperature RAT R/W °F -40 - 240 AV:135 rat_1
Setpoint Adjustment Enable STPT_ADJ_ENABLE R/W BV:6 stpt_adj_enable_1
Setpoint Adjustment Range STPT_ADJ_RANGE R/W AV:2 stpt_adj_range_1
Slow Change Cap Override SLO_CHNG R 0 - 1 BV:86 slo_chng_1
Smoke Purge Input PURG W 0 - 1 BV:1062 smk_purg_1
Soft Stop Request SOFTSTOP W 0 - 1 BV:87 softstop_1
SP High Alert Limit SPH R/W 2 0 - 5 AV:73 sph_1
SP Low Alert Limit SPL R/W 0 -0.5 - 5 AV:74 spl_1
SP Reset Limit SPRLIMIT R/W 0.75 0 - 2 AV:143 sprlimit_1
SP Reset Ratio SPRRATIO R/W 0.2 0 - 2 AV:144 sprratio_1
Space Enthalpy SPE R AV:71 spe_1
Space Relative Humidity SPRH R/W % 0 - 100 AV:72 sprh_1
Space Temp Offset Range SPTO_RNG R/W °^F 5 0 - 10 AV:139 spto_rng_1
Space Temperature SPT W °F -40 - 240 AV:137 spt_1