Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480114-01 Printed in U.S.A. Form 48/50N-2T Pg CL-1 7-14 Replaces: 48/50N-1T
ITEM EXPANSION RANGE DEFAULT SETTING
UNIT UNIT CONFIGURATION
C.TYP Machine Control Type 1 to 4 (multi-text strings) 3
SIZE Unit Size (75 - 150) 75 to 150 30
FN.MD Fan Mode (0=Auto, 1=Cont) 0 to 1 (multi-text strings) 1
RM.CF Remote Switch Config 0 to 3 (multi-text strings) 0
CEM CEM Module Installed No/Yes No
LQ.SN Liquid Sensors Installed No/Yes No
PW.MN Power Monitor Installed No/Yes No
VFD.B VFD Bypass Enable? No/Yes No
UVC.L UV-C Lamp Config? 0 to 2 (multi-text strings) 0
TCS.C Temp.Cmp.Strt.Cool Factr 0 to 60 min 0
TCS.H Temp.Cmp.Strt.Heat Factr 0 to 60 min 0
SFS.S Fan fail shuts down unit No/Yes No
SFS.M Fan Stat Monitoring Type 0 to 2 (multi-text strings) 0
VAV.S VAV Unocc.Fan Retry Time 0 to 720 min 50
MAT.S MAT Calc Config 0 to 2 (multi-text strings) 1
MAT.R Reset MAT Table Entries? No/Yes No
MAT.D MAT Outside Air Default 0 to 100% 20
ALTI Altitude........in feet: -1000 to 60000 0
DLAY Startup Delay Time 0 to 900 sec 0
AUX.R Auxiliary Relay Config 0 to 3 (multi-text strings) 0
SENS INPUT SENSOR CONFIG
SENSSPT.S Space Temp Sensor Disable/Enable Disable
SENSSP.O.S Space Temp Offset Sensor Disable/Enable Disable
SENSSP.O.R Space Temp Offset Range 1 to 10 5
SENSSRH.S Space Air RH Sensor Disable/Enable Disable
SENSRRH.S Return Air RH Sensor Disable/Enable Disable
SENSMRH.S Mixed Air RH Sensor Disable/Enable Disable
COOL COOLING CONFIGURATION
A1.EN Enable Compressor A1 Enable/Disable Enable
A2.EN Enable Compressor A2 Enable/Disable Enable
A3.EN Enable Compressor A3 Enable/Disable Enable
A4.EN Enable Compressor A4 Enable/Disable Enable
B1.EN Enable Compressor B1 Enable/Disable Enable
B2.EN Enable Compressor B2 Enable/Disable Enable
B3.EN Enable Compressor B3 Enable/Disable Enable
B4.EN Enable Compressor B4 Enable/Disable Enable
CS.A1 CSB A1 Feedback Alarm Enable/Disable Enable
CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable
CS.A3 CSB A3 Feedback Alarm Enable/Disable Enable
CS.A4 CSB A4 Feedback Alarm Enable/Disable Enable
CS.B1 CSB B1 Feedback Alarm Enable/Disable Enable
CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable
CS.B3 CSB B3 Feedback Alarm Enable/Disable Enable
CS.B4 CSB B4 Feedback Alarm Enable/Disable Enable
Z.GN Capacity Threshold Adjst 0.1 to 10.0 1
MC.LO Compressor Lockout Temp -25 to 55 dF 40
LLAG Lead/Lag Configuration 0 to 2 (multi-text strings) 0
HC.EV High Capacity Evaporator No/Yes No
H.ODF High Efficiency OD Fans? No/Yes No
M.M Motor Master Control ? No/Yes No
MM.OF MM Setpoint Offset -20 to 20 -10.0
CONTROLS SET POINT AND CONFIGURATION LOG
MODEL NUMBER: Software Version
SERIAL NUMBER: MBB CESR131461--
DATE: RXB CESR131465--
TECHNICIAN: EXB CESR131465--
NAVI CESR130227--
SCB CESR131226--
CEM CESR131174--
CXB CESR131173--
EXV CESR131172--
EXVA CESR131172--
EXVB CESR131172--