CL-6
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
IAQ (CONT)
CNN CCN CONFIGURATION
CNNCNN.A CCN Address 1 to 239 1
CNNCNN.B CCN Bus Number 0 to 239 0
CNNBAUD CCN Baud Rate 1 to 5 (multi-text strings) 3
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast Off/On On
BRODOAT.B CCN OAT Broadcast Off/On Off
BRODORH.B CCN OARH Broadcast Off/On Off
BRODOAQ.B CCN OAQ Broadcast Off/On Off
BRODGS.B Global Schedule Broadcst Off/On Off
BRODB.ACK CCN Broadcast Ack'er Off/On Off
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 to 99 1
SC.OVHOL.T Accept Global Holidays? No/Yes No
SC.OVOTL Override Time Limit 0 to 4 HRS 1
SC.OVOV.EX Timed Override Hours 0 to 4 HRS 0
SC.OVSPT.O SPT Override Enabled ? No/Yes Yes
SC.OVT58.O T58 Override Enabled ? No/Yes Yes
SC.OVGL.OV Global Sched. Override ? No/Yes No
ALLM ALERT LIMIT CONFIG.
ALLMSP.L.O SPT lo alert limit/occ -10 to 245 dF 60
ALLM
SP.H.O SPT hi alert limit/occ -10 to 245 dF 85
ALLMSP.L.U SPT lo alert limit/unocc -10 to 245 dF 45
ALLMSP.H.U SPT hi alert limit/unocc -10 to 245 dF 100
ALLMSA.L.O EDT lo alert limit/occ -40 to 245 dF 40
ALLMSA.H.O EDT hi alert limit/occ -40 to 245 dF 100
ALLMSA.L.U EDT lo alert limit/unocc -40 to 245 dF 40
ALLMSA.H.U EDT hi alert limit/unocc -40 to 245 dF 100
ALLMRA.L.O RAT lo alert limit/occ -40 to 245 dF 60
ALLMRA.H.O RAT hi alert limit/occ -40 to 245 dF 90
ALLMRA.L.U RAT lo alert limit/unocc -40 to 245 dF 40
ALLMRA.H.U RAT hi alert limit/unocc -40 to 245 dF 100
ALLMOAT.L OAT low alert limit -40 to 245 dF -40
ALLMOAT.H OAT high alert limit -40 to 245 dF 150
ALLMR.RH.L RARH low alert limit 0 to 100 % 0
ALLMR.RH.H RARH high alert limit 0 to 100 % 100
ALLMO.RH.L OARH low alert limit 0 to 100 % 0
ALLMO.RH.H OARH high alert limit 0 to 100 % 100
ALLMSP.L SP low alert limit -0.5 to 5 "H2O 0
ALLMSP.H SP high alert limit 0 to 5 "H2O 2
ALLMBP.L BP low alert limit -0.25 to 0.25 "H2O -0.25
ALLMBP.H
BP high alert limit -0.5 to 0.5 "H2O 0.25
ALLMIAQ.H IAQ high alert limit 0 to 5000 1200
TRIM SENSOR TRIM CONFIG.
TRIMSAT.T Air Temp Lvg SF Trim -10 to 10 ^F 0
TRIMRAT.T RAT Trim -10 to 10 ^F 0
TRIMOAT.T OAT Trim -10 to 10 ^F 0
TRIMSPT.T SPT Trim -10 to 10 ^F 0
TRIML.SW.T Limit Switch Trim -10 to 10 ^F 0
TRIMCCT.T Air Tmp Lvg Evap Trim -10 to 10 ^F 0
TRIMDTA.1 A1 Discharge Temp Trim -10 to 10 ^F 0
TRIMSP.A.T Suct.Press.Circ.A Trim -50 to 50 psig 0
TRIMSP.B.T Suct.Press.Circ.B Trim -50 to 50 psig 0
TRIMDP.A.T Dis.Press.Circ.A Trim -50 to 50 psig 0
TRIMDP.B.T Dis.Press.Circ.B Trim -50 to 50 psig 0
TRIMLP.A.T Lqd.Press.Circ.A Trim -50 to 50 0
TRIMLP.B.T Lqd.Press.Circ.B Trim -50 to 50 0
SW.LG SWITCH LOGIC:NO / NC
SW.LGPWS.L Power Fault Input - Good Open/Close Close
SW.LGMFT.L Filter Status Inpt-Clean Open/Close Open
SW.LGPFT.L Post Filter Stat. In-Cln Open/Close Open
SW.LGIGC.L IGC Feedback - Off Open/Close Open
SW.LGRMI.L
RemSw Off-Unoc-Strt-NoOv Open/Close Open
SW.LGENT.L Enthalpy Input - Low Open/Close Close
SW.LGSFS.L Fan Status Sw. - Off Open/Close Open
SW.LGDL1.L Dmd.Lmt.Sw.1 - Off Open/Close Open
SW.LGDL2.L Dmd.Lmt.Sw.2 - Off Open/Close Open
SW.LGIAQ.L IAQ Disc.Input - Low Open/Close Open
SW.LGFSD.L Fire Shutdown - Off Open/Close Open
SW.LGPRS.L Press. Switch - Off Open/Close Open
SW.LGEVC.L Evacuation Sw. - Off Open/Close Open
SW.LGPRG.L Smoke Purge Sw. - Off Open/Close Open
SW.LGDH.LG Dehumidify Sw. - Off Open/Close Open
SW.LGSFB.L SF Bypass Sw. - Off Open/Close Open
SW.LGPEB.L PE Bypass Sw. - Off Open/Close Open