CL-7
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
*Model number dependent.
ITEM EXPANSION RANGE DEFAULT SETTING
IAQ (CONT)
DISP DISPLAY CONFIGURATION
DISPTEST Test Display LEDs Off/On Off
DISPMETR Metric Display Off/On Off
DISPLANG Language Selection 0 to 1 (multi-text strings) 0
DISPPAS.E Password Enable Disable/Enable Enable
DISPPASS Service Password 0000 to 9999 1111
S.VFD SUPPLY FAN VFD CONFIG
S.VFDN.VLT VFD1 Nominal Motor Volts 0 to 999 volts 460*
S.VFDN.AMP VFD1 Nominal Motor Amps 0 to 999 amps 55.0*
S.VFDN.FRQ VFD1 Nominal Motor Freq 10 to 500 60
S.VFDN.RPM VFD1 Nominal Motor RPM 50 to 30000 1750
S.VFDN.PWR VFD1 Nominal Motor HPwr 0 to 500 40*
S.VFDM.DIR VFD1 Motor Direction 0 to 1 (multi-text strings) 0
S.VFDACCL VFD1 Acceleration Time 0 to 1800 sec 30
S.VFDDECL VFD1 Deceleration Time 0 to 1800 sec 30
S.VFDSW.FQ VFD1 Switching Frequency 0 to 3 (multi-text strings) 2
E.VFD EXHAUST FAN VFD CONFIG
E.VFDN.VLT VFD2 Nominal Motor Volts 0 to 999 volts 460*
E.VFDN.AMP VFD2 Nominal Motor Amps 0 to 999 amps 28.7*
E.VFDN.FRQ VFD2 Nominal Motor Freq 10 to 500 60
E.VFDN.RPM VFD2 Nominal Motor RPM 50 to 30000 1750
E.VFDN.PWR VFD2 Nominal Motor HPwr 0 to 500 20*
E.VFDM.DIR VFD2 Motor Direction 0 to 1 (multi-text strings) 0
E.VFDACCL VFD2 Acceleration Time 0 to 1800 sec 30
E.VFDDECL VFD2 Deceleration Time 0 to 1800 sec 30
E.VFDSW.FQ VFD2 Switching Frequency 0 to 3 (multi-text strings) 2
FLTC FILTER CONFIGURATION
FLTCFS.FT Filter Stat. Fault Timer 0 to 10 2
FLTCF.NOT Filter Notification Cut 20 to 50 25
FLTCF.ALT Filter Alert Cutoff 0 to 20 10
FLTCMFL.S Main Filter Status Cfg. 0 to 5 0
FLTCMF.TY Main Filter Type 0 to 9 0
FLTCMF.FR Main Filter Final Resis. 0 to 10 1
FLTCMF.LT Main Filter Life 0 to 60 12
FLTCMF.RM Main Filter Reminder 0 to 60 10
FLTCMF.RS Reset Main Filter Sched. No/Yes No
FLTCMF.ST Main Filter Status 0 to 100 0
FLTCMFT.R Reset MFT Table Entries? No/Yes No
FLTCPFL.S Post Filter Status Cfg. 0 to 5 0
FLTCPF.TY Post Filter Type 0 to 6 0
FLTCPF.FR Post Filter Final Resis. 0 to 10 1
FLTC
PF.LT Post Filter Life 0 to 60 12
FLTCPF.RM Post Filter Reminder 0 to 60 10
FLTCPF.RS Reset Post Filter Sched. No/Yes No
FLTCPF.ST Post Filter Status 0 to 100 0
FLTCPFT.R Reset PFT Table Entries? No/Yes No
PROG PROGNOSTICS CONFIG.
PROG LQ.SN Liquid Sensors Installed No/Yes No
PROG P.SPE Prognostics SP Enable Disable/Enable Disable
PROG PG.SP Prognostics SP Deadband 0 to 5 0.25
PROG P.BPE Prognostics BP Enable Disable/Enable Disable
PROG PG.BP
Prognostics BP Deadband 0 to 1 0.05
PROG AC.DB
EXV Superheat Deadband 0 to 2 2
PROG AC.SP
Auto-Comp Suct.Pres Drop 0 to 10 3
PROG AC.DS
Auto-Comp DS SP Drop 0 to 10 2.5
PROG ML.DR
MLV/HGBP DP Drop 0 to 2 5
PROG AC.CL
Low Charge Alert Cutoff -10 to 0 -3
PROG AC.CH
High Charge Alert Cutoff 0 to 10 1
PROG AC.MS
Min Charge SST 20 to 100 40