Table 3 HEATING RATING TABLE -- NATURAL GAS & PROPANE
UNITS GAS HEAT
AL/SS HEAT EXCHANGER
TEMP RISE
(DEG F)
THERMAL
EFFICIENCY
(%)
AFUE
(%)
INPUT / OUTPUT
STAGE 1 (MBH)
INPUT / OUTPUT
STAGE 2 (MBH)
Single Phase
04
LOW --- 72 / 56 25 --- 55 82% 79.1%
MED --- 115 / 89 55 --- 85 80% 78.5%
HIGH --- --- --- --- ---
05
LOW --- 72 / 56 25 --- 55 82% 79.1%
MED --- 115 / 90 35 --- 65 81% 79%
HIGH --- 150 / 117 50 --- 80 80% 78.8%
06
LOW --- 72 / 56 20 --- 55 82% 79.1%
MED --- 115 / 90 30 --- 65 81% 79%
HIGH --- 150 / 117 40 --- 80 80% 78.8%
Three Phase
04
LOW --- 72 / 56 25 --- 55 82% N/A
MED 82 / 66 115 / 89 55 --- 85 80% N/A
HIGH --- --- --- --- ---
05
LOW --- 72 / 56 25 --- 55 82% N/A
MED --- 115 / 90 35 --- 65 81% N/A
HIGH 120 / 96 150 / 117 50 --- 80 80% N/A
06
LOW --- 72 / 56 20 --- 55 82% N/A
MED --- 115 / 90 30 --- 65 81% N/A
HIGH 120 / 96 150 / 117 40 --- 80 80% N/A
07
LOW --- 72 / 59 15 --- 55 82% N/A
MED --- 115 / 93 25 --- 65 81% N/A
HIGH 120 / 96 150 / 120 35 --- 80 80% N/A
08
LOW --- 125 / 103 20 --- 50 82% N/A
MED 120 / 98 180 / 148 35 --- 65 82% N/A
HIGH 180 / 147 224 / 184 45 --- 75 82% N/A
09
LOW --- 125 / 103 20 --- 50 82% N/A
MED 120 / 98 180 / 148 30 --- 65 82% N/A
HIGH 180 / 147 224 / 184 40 --- 75 82% N/A
12
LOW 120 / 98 180 / 148 25 --- 65 82% N/A
MED 180 / 147 224 / 184 30 --- 65 82% N/A
HIGH 200 / 160 250 / 205 35 --- 70 80% N/A
14
LOW 120 / 98 180 / 148 20 --- 65 82% N/A
MED 180 / 147 224 / 184 25 --- 65 82% N/A
HIGH 200 / 160 250 / 205 25 --- 70 80% N/A
16
LOW 144 / 118 180 / 146 15 --- 55 81% N/A
MED 192 / 156 240 / 195 20 --- 60 81% N/A
HIGH 280 / 224 350 / 280 35 --- 65 80% N/A
NOTES:
Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m). For information on propane or altitudes above 2000
ft (610 m), see the Application Data section of this book. Accessory Propane/High Altitude kits are also available.
In the USA the input rating for altitudes above 2000 ft (610m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada,
the input rating must be derated by 10% for altit udes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.