11
Table 4 HEATING RATING TABLE -- LOW NO
X
1
UNIT
GAS
HEAT
LOW NOx HEAT EXCHANGER
TEMP RISE
(DEG F)
THERMAL
EFFICIENCY (%)
AFUE
(%)
INPUT / OUTPUT
STAGE 1 (MBH)
INPUT / OUTPUT
STAGE 2 (MBH)
Single Phase
04
LOW --- 60 / 47 20 --- 50 81% 80.6%
MED --- 90 / 72 30 --- 60 81% 80.6%
HIGH --- --- --- --- ---
05
LOW --- 60 / 47 20 --- 50 81% 80.6%
MED --- 90 / 72 30 --- 60 81% 80.6%
HIGH --- 120 / 97 40 --- 70 81% 81.5%
06
LOW --- 60 / 47 15 --- 50 81% 80.6%
MED --- 90 / 72 25 --- 60 80% 80.6%
HIGH --- 120 / 97 35 --- 70 80% 81.5%
Three Phase
04
LOW --- 60 / 47 20 --- 50 81% N/A
MED --- 90 / 72 30 --- 60 81% N/A
HIGH --- --- --- --- ---
05
LOW --- 60 / 47 20 --- 50 81% N/A
MED --- 90 / 72 30 --- 60 81% N/A
HIGH --- 120 / 97 40 --- 70 81% N/A
06
LOW --- 60 / 47 15 --- 50 81% N/A
MED --- 90 / 72 25 --- 60 80% N/A
HIGH --- 120 / 97 35 --- 70 80% N/A
NOTE:
1. Units meet California’s South Coast Air Quality Management District (SCAQMD) Low--- NO
x
emissions requirement of 40 nanograms per
joule or less.
--- N o t A p p l i c a b l e
Table 5 SOUND PERFORMANCE TABLE
UNIT
COOLING
STAGES
OUTDOOR SOUND (DB) @60HZ
A--WEIGHTED 63 125 250 500 1000 2000 4000 8000
A04 1 80 90.6 80.9 80.2 76 74.6 71.3 68.5 63.9
A05 1 81 90.9 84.6 79.5 77.9 76.5 71.1 66.9 62.5
A06 1 78 84.0 82.2 76.3 74.8 72.5 68.8 65.6 61.8
A07 1 78 88.8 81.8 76.9 74.4 73.3 69.8 66.3 62.7
A08 1 82 90.1 82.6 81.0 79.4 77.0 73.0 70.4 66.7
D08 2 82 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1
A09 1 83 91.2 86.4 81.9 81.0 78.3 73.9 71.4 67.3
D09 2 82 88.6 85.0 81.6 79.5 77.4 74.1 71.0 66.3
A12 1 82 88.6 85.0 81.6 79.5 77.4 74.1 71.0 66.3
D12 2 82 89.0 83.1 80.5 78.5 75.5 71.6 69.6 69.3
D14 2 87 87.0 85.2 84.6 84.9 82.2 78.4 75.3 72.9
D16 2 87 87.0 85.2 84.6 84.9 82.2 78.4 75.3 72.9
LEGEND
dB --- Decibel
NOTES:
1. Outdoor sound data is measure in accordance with AHRI
standard 270--- 2008.
2. Measurements are expressed in terms of sound power. Do
not compare these values to sound pressure values because
sound pressure depends on specific environmental factors
which normally do not match individual applications. Sound
power values are independent of the environment and there-
fore more accurate.
3. A--- weig hted sound ratings filter out very high and very low
frequencies, to better approximate the response of “average”
human ear. A--- weighted measurements for Carrier units are
taken in accordance with AHRI standard 270--- 2008.