9
Table 2 – AHRI COOLING RATING TABLE
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER
(KW)
SEER EER
IEER WITH
SINGLE SPEED
INDOOR
MOTOR
IEER WITH
2-- SPEED
INDOOR
MOTOR
A04 1 3 34.6 3.1 13.0 11.00 N/A N/A
A05 1 4 45.0 4.0 13.0 11.00 N/A N/A
A06 1 5 59.0 5.5 13.0 10.75 N/A N/A
A07 1 6 70.0 6.4 N/A 11.00 11.2 N/A
A08 1 7.5 88.0 8.0 N/A 11.00 11.2 N/A
D08 2 7.5 83.0 7.5 N/A 11.00 11.7 12.8
A09 1 8.5 97.0 8.8 N/A 11.00 11.2 N/A
D09 2 8.5 99.0 9.0 N/A 11.00 11.7 12.8
A12 1 10 117.0 10.6 N/A 11.00 11.2 N/A
D12 2 10 114.0 10.3 N/A 11.10 11.8 12.8
D14 2 12.5 140.0 12.9 N/A 10.80 11.0 11.8
D16 2 15 174.0 16.1 N/A 10.80 11.7 12.4
LEGEND
AHRI --- Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER --- Energy Efficiency Ratio
IEER --- Integrated Energy Efficiency Ratio
N/A --- Not Applicable
SEER --- Seasonal Energy Efficiency Ratio
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOTES:
1. Rated in accordance with AHRI Standard 210/240 or
340/360, as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F(27_C) db, 67_F(19_C) wb indoor
air temp and 95_F(35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling p art---
load EER efficiency for commercial unitary air conditioning
and heat pump equipment on the basis of weighted opera-
tion at various load capacities.
3. All 48TC units comply with ASHRAE 90.1 Energy Standard
for minimum SEER and EER requirements.
4. 48TC units comply with US Energy Policy Act (2005). To eval-
uate code compliance requirements, refer to state and local
codes.