14
Table 8 – PHYSICAL DATA (HEATING) 3 -- 6 TONS
48TC**04 48TC**05 48TC**06 48TC**07
Gas Connection
#ofGasValves 1 1 1 1
Nat. gas supply line press (in. w.g.)/ (PSIG) 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7
LP supply line press (in. w.g.) / (PSIG) 11 --- 13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 --- 13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47
Heat Anticipator setting (Amps)
1st stage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e 25 --- 55 25 --- 55 20 --- 55 15 --- 55
MED
#ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e 55 --- 85 35 --- 65 30 --- 65 25 --- 65
HIGH
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 2/3
Connection Size --- 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes --- 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e --- 50 --- 80 40 --- 80 35 --- 80
Liquid Propane Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e 25 --- 55 25 --- 55 20 --- 55 15 --- 55
MED
#ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e 55 --- 85 35 --- 65 30 --- 65 25 --- 65
HIGH
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 2/3
Connection Size --- 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T
Rollout switch opens / closes --- 195 / 115 195 / 115 195 / 115
Tem pe r at ur e R is e --- 50 --- 80 40 --- 80 35 --- 80
Low NOx Gas Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 ---
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Tem pe r at ur e R is e 20 --- 50 20 --- 50 15 --- 50 ---
MED
#ofstages/#ofburners(total) 1/3 1/3 1/3 ---
Connection Size 1 / 2 --- i n N P T 1 / 2 --- i n N P T 1 / 2 --- i n N P T ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Tem pe r at ur e R is e 30 --- 60 30 --- 60 25 --- 60 ---
HIGH
#ofstages/#ofburners(total) --- 1/3 1/3 ---
Connection Size --- 1 / 2 --- i n N P T 1 / 2 --- i n N P T ---
Rollout switch opens / closes --- 195 / 115 195 / 115 ---
Tem pe r at ur e R is e --- 40 --- 70 35 --- 70 ---
--- N o t a p p l i c a b l e