23
CURBS, WEIGHTS & DIMENSIONS (cont.)
C10299
Fig. 6 -- 48TC 08-- 12
C
D
A
B
C11247
Fig. 7 -- Service Clearance
LOC DIMENSION CONDITION
A
48--- in (1219 mm) Unit disconnect is mounted on panel
36--- in (914 mm) I f d i m e n s i o n --- B i s 1 2 --- i n ( 3 0 5 m m )
18--- in (457 mm) No disconnect, convenience outlet option
18--- in (457 mm) Recommended service clearance (use electric screwdriver)
12--- in (305 mm) Minimum clearance (use manual ratchet screwdriver)
B
36--- in (914 mm) Unit has economizer
12--- in (305 mm) I f d i m e n s i o n --- A i s 3 6 --- i n ( 9 1 4 m m )
Special Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36--- in (914 mm) Side condensate drain is used
18--- in (457 mm) Minimum clearance
D
48--- in (1219 mm) No flue discharge accessory installed, surface is combustible material
42--- in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36--- in (914 mm) Surface behind servicer is electrically non --- conductive (e.g., wood, fiberglass)
Special Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead
obstruction or vertical clearances.