Carrier WeatherMaker 48TC Series - Minimum Heating Entering Air Temperature; Troubleshooting Heating System

Carrier WeatherMaker 48TC Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
Table 23 COOLING CAPACITIES 2--STAGE COOLING 7.5 TONS
48TC08 COOLING CAPACITIES, UNIT WITH HUMIDI---MIZER SYSTEM IN SUBCOOLING MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- CFM
2250/0.05 3000/0.07 3750/0.09
A i r E n t e r i n g E v a p o r a t o r --- E w b ( F )
72 67 62 72 67 62 72 67 62
75
TC 103.05 93.02 83.60 109.77 99.52 90.08 114.01 103.69 95.19
SHC 43.66 55.34 67.09 50.99 66.29 81.31 57.49 76.27 92.20
kW 4.90 4.83 4.77 4.82 4.88 4.96 4.99 4.91 4.85
85
TC 95.39 85.83 76.88 101.59 91.89 82.95 105.53 95.76 87.77
SHC 36.42 48.47 60.60 43.24 58.99 74.40 49.44 68.68 84.90
kW 5.49 5.42 5.36 5.40 5.47 5.54 5.58 5.50 5.44
95
TC 87.48 78.44 69.97 93.21 84.05 75.61 96.84 87.63 80.14
SHC 28.98 41.46 53.97 35.32 51.53 67.34 41.21 60.92 77.41
kW 6.16 6.09 6.03 6.08 6.14 6.21 6.24 6.17 6.11
105
TC 79.35 70.83 62.84 84.57 75.96 68.04 87.88 79.23 72.26
SHC 21.34 34.26 47.18 27.17 43.86 60.08 32.73 52.95 69.70
kW 6.93 6.86 6.81 6.85 6.91 6.97 7.00 6.93 6.88
115
TC 70.87 62.89 55.42 75.58 67.54 60.15 78.56 70.51 64.06
SHC 13.40 26.79 40.14 18.70 35.89 52.54 23.94 44.68 61.67
kW 7.79 7.74 7.69 7.73 7.78 7.83 7.86 7.80 7.76
48TC08 COOLING CAPACITIES, UNIT WITH HUMIDI---MIZER SYSTEM IN HOT GAS REHEAT MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(56% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
A i r E n t e r i n g E v a p o r a t o r --- C f m
2250 3000 3750 2250 3000 3750 2250 3000 3750
80
TC 27.60 32.75 30.19 40.09 39.43 37.73 45.06 45.25 44.25
SHC --- 3.12 5.20 6.71 3.75 5.24 6.75 3.77 5.26 6.78
kW 4.56 4.51 4.46 4.63 4.60 4.56 4.70 4.67 4.64
75
TC 35.40 33.78 31.20 41.14 40.51 38.80 46.15 46.37 45.38
SHC 4.67 6.17 7.69 4.71 6.21 7.73 4.74 6.24 7.76
kW 4.41 4.36 4.39 4.41 4.36 4.36 4.41 4.39 4.36
70
TC 36.36 34.71 32.18 42.10 41.47 39.77 47.08 47.31 46.32
SHC 5.63 7.14 8.66 5.67 7.18 8.71 5.70 7.21 8.74
kW 4.43 4.49 4.41 4.44 4.40 4.39 4.49 4.47 4.44
60
TC 38.25 36.64 34.15 43.97 43.37 41.72 48.98 49.22 48.26
SHC 7.56 9.09 10.62 7.60 9.13 10.66 7.62 9.15 10.69
kW 4.56 4.55 4.43 4.57 4.53 4.46 4.56 4.55 4.50
50
TC 40.15 38.60 36.14 45.95 45.37 43.73 50.57 50.97 49.56
SHC 9.48 11.03 12.58 9.52 11.07 12.62 9.54 11.10 12.64
kW 4.63 4.52 4.38 4.45 4.41 4.33 5.25 4.91 5.60
40
TC 42.18 40.62 38.11 47.80 47.25 45.43 52.65 52.75 51.83
SHC 11.41 12.98 14.54 11.45 13.02 14.58 11.47 13.04 14.60
kW 4.32 4.37 4.37 4.65 4.60 4.89 4.96 5.20 5.12
LEGEND
E d b --- E n t e r i n g D r y --- B u l b
E w b --- E n t e r i n g W e t --- B u l b
kW --- Compressor Motor Power Input
I d b --- L e a v i n g D r y --- B u l b
I w b --- L e a v i n g W e t --- B u l b
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC --- Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The f ollowing formulas may be used:
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet--- bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalpy of air entering evaporator coil

Other manuals for Carrier WeatherMaker 48TC Series