R410a DC Inverter 60Hz Carrier service manual
146 Installation
7. Electrical Engineering
7.1 Wiring terminals instruction
7.2 Power supply wiring installation
7.2.1 Outdoor unit power supply wiring
7.2.2 Indoor unit power supply wiring
Note:
Set refrigerant piping system, signal wires between indoor units and signal wires between outdoor units into one
system.
Power must unified supply to all indoor units in the one system.
Please do not put the signal wires and power wires in the same wire tube; keep distance between the two tubes. (Keep
distance above 300mm; when current capacity of power supply less than 10A, and Keep distance above 500mm, when
current capacity of power supply less than 50A).
Make sure to address the outdoor unit which is in combination type.
7.2.3 Electric characteristics
Model
Outdoor Unit Power Supply Compressor OFM
Hz Voltage Min. Max. MCA TOCA MFA MSC RLA kW FLA
38VF008H117010
60 208 188 253 36.0 35.0 40 - 35.5 0.42 4.4
38VF010H117010
60 208 188 253 36.0 35.0 40 - 35.5 0.42 4.4
38VF012H117010
60 208 188 253 46.5 49.5 55 - 35.5+21.1 0.22*2 2.2*2
38VF014H117010
60 208 188 253 54.6 54.4 60 - 35.5+21.1 0.36×2 3.4×2
38VF016H117010
60 208 188 253 54.6 54.4 60 - 35.5+21.1 0.36×2 3.4×2
38VF018H117010
60 208 188 253 54.6 54.4 60 - 35.5+21.1 0.36×2 3.4×2
Three-phase power supply
A B C N
Outdoor units
communication
Network
accounting
Indoor units
centralized
contros
Indoor units
communication
Outdoor units
centralized
monitoring
Leakage protector
Manual switch
Branch box
Indoor unit
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16