R410a DC Inverter 60Hz Carrier service manual
148 Installation
7.3.2 Example connection of wiring
(P Q E)
(H1 H2 E) (H1 H2 E) (H1 H2 E)
(H1 H2 E)
(P Q E)
Signal wire between outdoor units
To closed end of shield wire
(open)
group control
The indoor unit at the terminal of communication system should
parallel connect a resisitor between port P and port Q.
P
Q
matching
resisitor
(master unit)
(slave unit)
(slave unit)
(slave unit)
Signal wire between
indoor and outdoor units
All shield terminals of shield wires
should connect to COMM terminal