R410a DC Inverter 60Hz Carrier service manual
22 Specification & Performance
Throttle type EXV EXV EXV
Excessive operating pressure psi(MPa) 638/377(4.4/2.6) 638/377(4.4/2.6) 638/377(4.4/2.6)
Liquid side/ Gas side in.(mm) 5/8(Ф15.9)/1-1/4(Ф31.8) 5/8(Ф15.9)/1-1/4(Ф31.8) 3/4(Ф19.1)/1-1/4(Ф31.8)
Ambient temperature range
Cooling
()
23~118.4(-5~48) 23~118.4(-5~48)
Heating
()
-4~75.2(-20~24) -4~75.2(-20~24)
Notes:
1. The cooling conditions: indoor temperature: 27DB(80.6), 19WB(60), outdoor temperature: 35DB(95), equivalent pipe length: 16.4ft(5m), drop
length: 0m.
2. The heating conditions: indoor temperature: 20DB(68), 15WB(59) outdoor temperature: 7DB(44.6) equivalent pipe length: 16.4ft(5m ), drop
length: 0m.
3. Sound values are measured in a semi-anechoic room, at a position 3.28ft(1m) in front of the unit and 4.26ft(1.3m) above the floor.
4. The above data may be changed without notice for future improvement on quality and performance.