Carrier service manual R410a DC Inverter 60Hz
Installation 103
OD:12.7
ID:9.5
ID:9.5
OD:9.5
ID:6.4
OD:9.5
ID:9.5
L4/D N3+N4=280 230≤A<330
Φ7/8(Φ22.2)/Φ3/8(Φ9.53)
BJF-330-CM(i)
L2/B N1+……+N4=560 460≤A<660
Φ1-1/8(Φ28.6)/Φ5/8(Φ15.9)
BJF-710-CM(i)
L7/G N6+N7=142 A<166
Φ5/8(Φ15.9)/Φ3/8(Φ9.53)
BJF-224-CM(i)
L6/F N5+……+N7=282 230≤A<330
Φ7/8(Φ22.2)/Φ3/8(Φ9.53)
BJF-330-CM(i)
L9/I N9+N10=136 230≤A<330
Φ7/8(Φ22.2)/Φ3/8(Φ9.53)
BJF-330-CM(i)
L8/H N8+……+N10=276 230≤A<330
Φ7/8(Φ22.2)/Φ3/8(Φ9.53)
BJF-330-CM(i)
L5/E N5+……+N10=558 460≤A<660
Φ1-1/8(Φ28.6)/Φ5/8(Φ15.9)
BJF-710-CM(i)
L1/A N1+……+N10=1118 920≤A<1350
Φ1-1/2(Φ38.1)/Φ3/4(Φ19.1)
BJF-1344-CM(i)
1.1.3.3 Select main pipe(L1) and outdoor unit pipe(g1-g3,G1),outdoor branch,
Main
unit
pipe/branch
Model
The Max. equivalent pipe length≥ 90m
Range Branch Refer to
Gas Side/ Liquid Side
g1 10HP
Φ1(Φ25.4)(Welding)/Φ1/2(Φ12.7)(Flaring Nut)
8≤W3≤10HP /
the table
4-7
g2 14HP
Φ1-1/4(Φ31.8)(Welding)/Φ5/8(Φ15.9)(Flaring Nut)
12≤W2≤16HP /
g3 16HP
Φ1-1/4(Φ31.8)(Welding)/ Φ5/8(Φ15.9)(Flaring Nut)
12≤W1≤16HP /
G1 24HP Φ1-1/2(Φ38.1)Welding)/Φ19.1(Welding)
Two modular
combination
/
L1 40HP Φ1-1/2(Φ38.1)(Welding)/Φ19.1(Welding) 34-48HP /
the table
4-5
L+M / /
Three
combination
BJC-03-CM(I)
the table
4-7
1.1.3.4 Compare the total capacity from indoor side and outdoor side, select the main pipe
diameter according to the bigger one.
Main pipe L1 in the Fig.4-3, which upstream outdoor units total capacity is 10+12+16=38, base on table.4-5,
the gas/liquid pipe diameter are Φ1-1/2(Φ38.1)/Φ7/8(Φ22.2), total capacity of the downstream indoor unit is
140×6+56×2+71×2=1094, based on table.4-4, the gas/liquid pipe diameter are Φ1-1/2(Φ38.1)/Φ3/4(Φ19.1),
take the large one for your selection, final confirm the main pipe diameter is: gas/liquid pipe
Φ1-1/2(Φ38.1)/Φ7/8(Φ22.2).
1.1.4 Branch drawing
1.1.4.1 Indoor branch drawing
Indoor
branch
Gas side Liquid side
BJF-224-CM(
I)
ID:12.7
(ID:15.9)
OD:19.1
ID:19.1
OD:19.1
ID:19.1
ID:15.9
(ID:15.9)
OD:19.1