62-11637 7–32
00059 DATALOGGER (DataLink data recorder) NOT RECORDING
ACTIVATION: No data is being recorded by the DataLink data recorder.
UNIT CONTROL: Alarm only.
RESET CONDITION: Alarm may be manually reset using the display mounted keys.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Clear Alarm
a. Clear Active Alarm(s).
b. Check for Active Alarm re-occurrence. If Inactive, download all data & retain. If Active, go to next step.
2. Main Microprocessor Defective
a. Download previous data using a Data Transfer USB memory device, or TRU-Tech. Data retrieval OK.
b. Replace and setup main microprocessor. Refer to Section 5.5.
NOTE
Specific Configurations may be found on the TransCentral Website (Authorized Carrier Transicold
Dealers only).
00060 DATALOGGER (DataLink data recorder) TIME WRONG
ACTIVATION: The real time clock in the DataLink data recorder does not contain a valid date.
UNIT CONTROL: Alarm only.
RESET CONDITION: Auto reset when the DataLink data recorder real time clock is reset, or alarm may be
manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1. Check Real Time Clock
Check Real Time Clock in the Unit Data, or using TRU-Tech. Must show correct date and time.
Change as needed. Refer to Section 5.2.3.
2. Reset Microprocessor
a. Place the SROS in the OFF position for 30 seconds and then return it to the START/RUN position.
Verify microprocessor powers up OK.
b. Check for valid real time clock reading in Unit Data. Alarm is cleared automatically.
c. Real Time Clock can not be changed. Proceed to step 3.
3. Main Microprocessor Defective
a. Download previous data using a Data Transfer USB memory device, or TRU-Tech. Verify data
retrieval OK.
b. Replace and setup main microprocessor. Refer to Section 5.5.