EasyManua.ls Logo

Carrier X4 7300 - 22102 Sensor Input Voltage High Inp1; 23100 No Comm from Micro to Outpbd1

Carrier X4 7300
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7–85 62-11637
22102 SENSOR INPUT VOLTAGE HIGH INP1
NOTE
This alarm is an indication that there is a short in the DC current transformer wiring from another (nom-
inal 12 VDC) circuit into the transducer or CT sensor circuit.
ACTIVATION: Voltage from main microprocessor to the sensors is greater than 5.5 VDC
UNIT CONTROL: Alarm only.
RESET CONDITION: Auto reset when sensor voltage is correct, alarm reset or alarm may be manually reset
by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check Transducer Wiring
Check wires to sensors for short.
For CSP, check wiring from 2MM20, 2MM30 and 2MM9.
For EVOP, check wiring from 2MM28, SP7 and 2MM17.
For CDP, check wiring from 2MM21, SP7 and 2MM10.
2. Check CT Wiring
Check wires to sensor for short from another circuit. Check wiring from 2MM29, 2MM12 and 2MM23
to PCM.
3. Replace Main Microprocessor
Download data and replace main microprocessor. For complete Main Microprocessor Module replace-
ment instructions refer to Section 5.5.2.
23100 NO COMM FROM MICRO TO OUTPBD1
ACTIVATION: Main microprocessor cannot communicate internally.
UNIT CONTROL: Shutdown all modules except the display and alarm. (The alarm will only display if the dis-
play module is communicating.) Main microprocessor status LED will illuminate steady green (not pulsing).
RESET CONDITION: Auto reset when internal communication is restored, alarm reset or alarm may be
manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Replace Main Microprocessor
Download data and replace main microprocessor. For complete Main Microprocessor Module replace-
ment instructions refer to Section 5.5.2.

Table of Contents

Related product manuals