CG Drives & Automation 01-5326-01r5 Technical Data 249
Note: For IP54 models 48/52-003 to -074 and 69-002 to -058 cable glands are optional.
* IP20/21 models are equipped with cable clamps instead of glands.
For data on cable connection ranges, see section 3.4.3, page 39.
##-205-20 178 200
- (48 - 52 mm(1.89 - 2.05 in)/
52 - 56 mm (2.05 - 2.2 in))
- (44 - 48 mm (1.73 - 1.89 in))
##-210-54 182 200
(Ø23 - 55 mm (0.9 - 2.16 in))
cable flexible leadthrough or M63
opening.
(Ø17- 42 mm (0.67 - 1.65 in))
cable flexible leadthrough or M50
opening.
##-228-54 197 250
##-244-20 211 250
- (48 - 52 mm (1.89 - 2.05 in)/
52 - 56 mm (2.05 - 2.2 in))
- (44 - 48 mm (1.73 - 1.89 in))
##-250-54 216 250
(Ø 23 - 55 mm (0.9 - 2.16 in))
cable flexible leadthrough or M63
opening.
(Ø 23 - 55 mm (0.9 - 2.16 in))
cable flexible leadthrough or M63
opening.
##-295-54 256 300
##-293-20 254 300
- (48 - 52 mm (1.89 - 2.05 in)/
52 - 56 mm (2.05 - 2.2 in))
- (44 - 48 mm (1.73 - 1.89 in))
##-365-54 324 355
(Ø 23 - 55 mm (0.9 - 2.16 in))
cable flexible leadthrough or M63
opening.
(Ø 23 - 55 mm (0.9 - 2.16 in))
cable flexible leadthrough or M63
opening.
#-365-20 324 355 M10 bolt for cable lugs M8 bolt for cable lugs
##-300-54 260 300
-- --
##-375-IP 324 355
69-400-IP 346 400
##-430-IP 372 400
##-500-IP 432 500
##-600-IP 520 630
##-650-IP 562 630
##- 720, 750-
IP
648 710
##-860-IP 744 800
##-900-IP 795 900
##-1K0-IP 864 1000
##-1K15-IP 996 1250
##-1K2-IP 1037 1250
##-1K25-IP 1037 1250
##-1K35-IP 1170 1250
##-1K5-IP 1296 1500
##-1K75-IP 1516 1600
##-2K0-IP 1732 2 x 900
##-2K25-IP 1949 2 x 1000
##-2K5-IP 2165 2 x 1250
Table 65 Fuses, cable cross-sections and glands for VFX48 and VFX52 models
Model VFX
Nominal input
current
[A]
Maximum
value fuse
[A]
Cable glands (clamping range ) *
mains / motor Brake