15
Product Manual - Trifecta
®
XPro Series
Parameter Settings
Initial power up from the factory will require some
the lower line of the main display. No valves will operate
weeks.
Reset Values
the MON/OFF/RUN switch found on the front of the control
the lower line of the main display. The valves will not be
controlled by the PLC when “Monitor” is in the display.
Note:
operations continue. Reset parameters
position.
Operation
Setting Pressure Set Points
Three settable parameters are accessible from the PLC
buttons. These parameters are key to setting all parameters.
• Pressing the “Left” arrow button accesses the pressure
building set points.
•
“PBOn” set point.
• At the “PBOn” pressure the system turns on the primary
tanks PB valve.
•
• The secondary tanks PB “Hold” pressures are a function
of these values.
• Pressing and holding the “Left” arrow and pressing the
“+” button or the “-” button will adjust the set points.