R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
68
GD Chigo Heating & Ventilation Equipment Co., Ltd.
5.5 CTH-48CR1, CTH-60CR1
6.Capacity Tables
Cooling
6.1 CTA-18HR1
CTA-18CR1
MODEL
CTA-18HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
43ºC
21ºC D 15ºC W
Total capacity kW
5.50
5.45
5.39
5.31
4.77
4.05
Input kW.
1.53
1.57
1.65
1.65
1.75
1.82
24ºC D 17ºC W
Total capacity kW
5.78
5.72
5.67
5.58
5.01
4.26
Input kW.
1.57
1.60
1.63
1.68
1.78
1.85
27ºC D 19ºC W
Total capacity kW
6.07
6.01
5.95
5.86
5.26
4.47
Input kW.
1.60
1.63
1.66
1.71
1.82
1.89
29ºC D 19ºC W
Total capacity kW
6.31
6.07
6.01
5.92
5.31
4.51
Input kW.
1.63
1.56
1.59
1.64
1.74
1.81
32ºC D 23ºC W
Total capacity kW
6.56
6.50
6.44
6.34
5.69
4.83
Input kW.
1.66
1.70
1.73
1.78
1.89
1.97