Earth fault protection
If=
Acting property
Setting current
(0.2~1.0)In + OFF (with 160A as the minimum and 1200A as the maximum.
OFF means it only alarms without tripping)
0.8If without actions
1.0 If delayed action
.47.
Air Circuit Breaker
e.Instruction to technical property
Ir2=
Ir3=
Acting property
Acting property
Setting current
Setting current
g.Instruction to short time-delay property
(1.5~15) Ir1 + OFF (exit position)
0.9Ir2 without actions
1.1Ir2 delay action
(0.1~1)s (0.1s level error)
±10% (intrinsic 40ms)
Curve is the same as overload long delay, but curve speed is 10 times faster.
Standard + OFF
Ts=
Precision
Inverse-time delay (s)
(Corresponding 2Ir1)
Inverse-time property
Short delay inverse-time thermal memory (15min)
h.Instruction to short circuit instantaneous property
1.01n~50kA/75kA/100kA+OFF (Exit position)
0.85Ir3 without actions
1.15Ir3 with actions
Note: When controller is frame I (Inm=2000A), rectified value of instantaneous protection is 1.0In~50kA+OFF; when controller is frame II
(Inm=3200A), rectified value of instantaneous protection is 1.0In~75kA+OFF; When controller is frame III (Inm=6300A), rectified value
of instantaneous protection is 1.01n~100kA+OFF.
i.Earth fault or residual current protective property: t=TG×KG×If/I
Ir1=
Acting property
Setting current
Property curve
Curve speed
Precision
Inverse-time (s)
(Corresponding 2Ir1)
Electrical machine protection
Thermal memory (30min, could be eliminated
while power-off)
Standard + OFF
100% or 50% (Applicable to 3P+N or 4P products)
N-phase overload and over-current property
Note: When N-phase is 50%, protective settings are treated as 50% for N-phase. If long delay setting is 2000A, long delay setting for phase A, B
and C is 2000A, and 1000A for phase N.
(0.4~1.25)In + OFF (Exit position)
I1.05Ir1 without actions in 2h
I1.20Ir1 with actions while it's less than 1h
Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory
IEC255 standard, 80 level points totally, could be rectified
±10% (intrinsic 40ms)
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20
t(s)
Xin1
Express inverse-time 1
(Ordinary use)
Express inverse-time 2
(Motor protection)
Express inverse-time
Standard
inverse-time
High-voltage fuse
compatibility
f. Overload long time-delay protection
Power distribution or motor protection
(0.4~1.0)In + OFF (Exit position)
I1.05Ir1 without actions in 2h
I1.20Ir1 with actions while it's less than 1h
Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory
IEC255 standard, 80 level points totally, could be rectified
±10% (intrinsic 40ms)
Ir1=
Acting property
Setting current
Property curve
Curve speed
Precision
Inverse-time (s)
(Corresponding 2Ir1)
.46.