Page 38 of 40 IRIS Touch Engineering Manual Version 1.4
12. Specifications
Transmission paths
600NG
620NG
640NG
Ethernet
Standard
UTP 10/100 Base T with auto-negotiation
Connection
RJ45 socket for CAT5 cabling
IP addressing
Dynamic (DHCP) or fixed
Connection
fault detection
Loss of Ethernet synchronisation
GPRS/3G
(4G/CDMA optional
on request)
Standard
Dual band GSM
900/1800 MHz
Dual band UMTS
900/2100 MHz
Dual band GSM
900/1800 MHz
Dual band UMTS
900/2100 MHz
Connection
SMA socket for GPRS/3G
antenna connection
SMA socket for GPRS/3G
antenna connection
Connection
fault detection
Loss of registration with
network
Loss of registration with
network
IP
TCP ports (outbound)
53165 (Alarms & Polling), 51292 (Diagnostic & Reflashing), 10001 (Upload/Download)
Alarm transmission
Interface to monitoring centre
IRIS Secure Apps or IRIS Management Suite via EN 50136-2 pass-through mode
Serial interface to alarm panel
RS485, TTL, RS232 x 2 Note: RS232 cabling must not exceed 30 meters
PIN Inputs interface to alarm panel
Maximum input voltage range 0V to +24V
Input ‘low’ (alarm) threshold < 1V
Input ‘high’ (restore) threshold > 2V
Internal pull-up impedance 10K to 3.3V supply
Alarm protocols
SIA (level 1 to 3) reference SIA DC-03-1990.01(R2003.10)
Contact ID reference SIA DC-05-1999.09
Fast format (Scancom)
Tamper detection reporting to
monitoring centre
Serial interface, Pin inputs
Fault reporting to monitoring centre
Transmission interface/path fault
Relay outputs
Maximum operating voltage
24V DC
Maximum current rating
100mA DC
Power supply
Supply voltage
9V to 28V DC
Note: For Radio & Telecoms Terminal Equipment Directive the power cable needs to
be no longer than 3 meters in length
Typical current
97mA @ 12V DC
98mA @ 12V DC
106mA @ 12V DC
Maximum current
1A @ 12V DC
Recommended external PSU
12V DC 1A 12 Watt
Environmental
Operating temperature range
-10°C to 55°C
Operating humidity range
95% max, non-condensing
Weights and dimensions
Physical dimensions
12 cm x 9 cm
PCB weight
60 grams
Fully packaged weight
160 grams