Programmable AC Source 61601/61602/61603/61604 User’s Manual
7.6.2.2 OUTPUT Sub-system
OUTPut
[: STATe]
: RELay
: SLEW
: VOLTage
: AC
: DC
:FREQuency
:COUPle
:PROTection
:CLEar
OUTPut [: STATe]
Description : This command enables or disables the output of the AC source.
Disable output is to set an output voltage amplitude at 0 Volt.
Query Syntax : OUTPut [: STATe]?
Parameters : OFF | ON
Return Parameters : OFF | ON
OUTPut : RELay
Description : This command sets output relay on or off.
Query Syntax : OUTPut : RELay?
Parameters : OFF | ON, ON sets the output relay of the AC source on
(closed). OFF sets the output relay of the AC source off (open).
Return Parameters : OFF | ON
OUTPut : SLEW : VOLTage : AC
Description : This command sets the slew rate of the AC output voltage.
Query Syntax : OUTPut : SLEW : VOLTage : AC?
Parameters : <NR2>, valid range: 0.000V/ms ~ 1200.000V/ms
Return Parameters : <NR2>
OUTPut : SLEW : VOLTage : DC
Description : This command sets the slew rate of the DC composition
voltage.
Query Syntax : OUTPut : SLEW : VOLTage : DC?
Parameters : <NR2>, valid range: 0.000V/ms ~ 1000.000V/ms
Return Parameters : <NR2>
OUTPut : SLEW : FREQuency
Description : This command sets the slew rate of the output frequency.
Query Syntax : OUTPut : SLEW : FREQuency?
Parameters : <NR2>, valid range: 0.000 Hz/ms ~ 1000.000Hz/ms
Return Parameters : <NR2>
OUTPut : COUPling
Description : This command selects the couple setting of the output signal.
Query Syntax : OUTPut : COUPling?
Parameters : AC | DC | ACDC
Return Parameters : AC | DC | ACDC
OUTPut : PROTection : CLEar