EasyManua.ls Logo

CIAT GeoCIAT - On;Off Control Input Operations

CIAT GeoCIAT
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN - 46
5.6 On/Off control inputs
5.6.1 Turning off or 'bypassing' your heat pump or the heating elements via remote control
To shut down the heat pump and/or heating elements via remote control, remove the jumper on connector J11 terminals 1 and 2
from the HomeConnect controller. Connect your contact between these two terminals.
Contact quality: compatible with a 10 mA current at 24 V.
1: contact closed: normal operation
2: contact open:
- In heating mode, the bypass depends on parameter P13 (see table below).
- In absence mode, the bypass is not operational.
5.6.2 Turning on the frost protection via remote control: P15 = ABSENCE
To place your system in frost-free mode by remote control, set parameter P15 to ABSENCE. Connect a contact to connector J11
terminals 2 and 3 on your unit's HomeConnect controller.
Contact quality: compatible with a 10 mA current at 24 V.
1: contact closed: unit operated by the terminal,
2: contact open: unit operates in Absence mode.
5.6.3 Turning on cooling/heating mode by remote control: P15 = COOLING/HEATING
To activate heating mode by remote control, set parameter P15 to COOLING/HEATING. Connect a contact to connector J11
terminals 2 and 3 on your unit's HomeConnect control board.
Contact quality: compatible with a 10 mA current at 24 V.
1: contact closed: forced operation in heating mode.
2: contact open: the heat pump is turned off.
Note: the Heating menu
is no longer visible in the control terminal's main menu.
5.6.4 Turning on the Domestic Hot Water cycle via remote control: P15 = DHW
To turn on the Domestic Hot Water cycle by remote control, set parameter P15 to DHW. Connect a contact to connector J11
terminals 2 and 3 on your unit's HomeConnect control board.
Contact quality: compatible with a 10 mA current at 24 V.
1: contact closed: DHW cycle restarted then unit operated by the terminal.
2: contact open: unit operated by the terminal.
Usage example: connection to an off-peak/peak times contact to produce domestic hot water during off-peak times.
Bypass control
(value of P13)
Type of bypass (via opening of contact)
Heat pump Heat pump turned off
HEATING ELEMENT Heating elements turned off
HP + HEATING ELEMENT
Heat pump and heating elements turned off (application example:
entire heating system turned off remotely)