NA 12.54 D EN - 8
Parameter Name Explanation Setting range
Default
value
Param. written on
slave
P12 Sensor S1 calibration
Correction factor for sensor S1 - 9.9...+ 9.9
resolution of 0.1
0
P13
Indoor environment
sensor calibration
Correction factor for the room sensor - 9.9...+ 9.9
resolution of 0.1
0
P14
Action direction of
auxiliary contact on
input D1
The auxiliary contact on input DI1 may be normally closed
or normally open:
0 = Normally open
1 = Normally closed
0 : 1 1 X
P15
Action direction of
auxiliary contact on
input D2
The auxiliary contact on input DI2 may be normally closed
or normally open:
0 = Normally open
1 = Normally closed
0 : 1 1 X
P16 Input D1 function
This parameter allows the input to have several functions:
0 = Inactive on control
1 = Frost protection
2 = Economy
3 = Alarm
4 = LS air purification
5 = MS air purification
6 = Off
0...6 1 X
P17 Input D2 function
This parameter allows the input to have several functions:
0 = Inactive on control
1 = Frost protection
2 = Economy
3 = Alarm (HEE motor)
4 = LS air purification
5 = MS air purification
6 = Off
0...6 3 X
P18 Number of fan speeds
0 = 3 speeds in all modes
1 = 3 speeds in comfort mode/2 speeds in reduced mode
0 : 1 0 X
P19 Deadband ventilation
0 = Ventilation off in all modes
1 = Periodic restarts in comfort mode/off in economy and
frost protection mode
2 = Periodic restarts in all modes
3 = Permanent ventilation in comfort mode/off in economy
and frost protection mode
4 = Permanent ventilation in comfort mode/periodic restarts
in economy and frost protection modes
5 = Permanent ventilation in cooling comfort mode/off in
heating comfort, economy and frost protection mode
6 = Permanent ventilation in cooling comfort mode/
periodic restarts in heating comfort, economy and frost
protection modes
7 = Permanent ventilation in cooling comfort mode/periodic
restarts in heating comfort mode/off in economy and
frost protection mode
0...7 0 X
P20 Electric heater operation
0 = Electric heater disabled
1 = Electric heater in main heating mode only
2 = Auxiliary electric heater only
3 = Electric heater in main heating + auxiliary mode
0 : 1 : 2 : 3 3 X