1-50
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Step 1 For an ONS 15454 ETSI shelf, complete the following tasks as necessary:
Complete the “DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)” task on page 1-50 if
you want to provision external alarms and/or controls with the AIC-I card.
Complete the “DLP-G21 Install Timing Wires on the MIC-C/T/P (ETSI Only)” task on page 1-53 if
you are provisioning external timing.
Complete the “DLP-G22 Install LAN Wires on the MIC-C/T/P (ETSI Only)” task on page 1-54 to
create an external LAN connection. You must either install LAN wires on the MIC-C/T/P or connect
a CAT-5 Ethernet cable to the LAN port on the TCC2/TCC2P card to create an external LAN
connection.
Step 2 For an ONS 15454 ANSI shelf, complete the following tasks as necessary:
Complete the “DLP-G23 Install Alarm Wires on the Backplane (ANSI Only)” task on page 1-55 if
you are using an AIC-I card and are not using an AEP.
Complete the “DLP-G24 Install Timing Wires on the Backplane (ANSI Only)” task on page 1-57 if
you are provisioning external timing.
Complete the “DLP-G25 Install LAN Wires on the Backplane (ANSI Only)” task on page 1-58 to
create an external LAN connection. You must either install LAN wires on the backplane or connect
a CAT-5 Ethernet cable to the LAN port on the TCC2/TCC2P card to create an external LAN
connection.
Complete the “DLP-G26 Install the TL1 Craft Interface Wires (ANSI Only)” task on page 1-59 to
access Transaction Language One (TL1) using the craft interface. Craft wires or the EIA/TIA-232
port on the TCC2/TCC2P card are required to access TL1.
Stop. You have completed this procedure.
DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Step 1 Using 0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires, connect the alarm and control wires on the
appropriate pins of the DB-62 connector. The pin connectors, signal names, and functions are listed in
Table 1-3.
Purpose This task installs alarm cables on the MIC-A/P on the ONS 15454 ETSI so
that you can provision external (environmental) alarms and controls with
the AIC-I card.
Tools/Equipment DB-62 connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires
Prerequisite Procedures NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), page
1-30
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None