3. CC-Link Communication Function
[SMF-2008-A]
– 3-13
iii) Setting of CC-Link station information
ABSODEX: Remote device station, 2 stations occupied.
At this time, if the station number is not 1, the corresponding station number should be the
similar setting.
Fig. 3.11. Setting of remote device station
iv) Check of device
If the remote input (RX) is set as “X1000”, ABSODEX is station number 1, so RXn0: M code
output (bit 0) corresponds to X1000.
Remaining output signals correspond in order for example, RXn1 = X1001, RXn2 =
X1002, ...
Fig. 3.12 Screen example of device monitor
Other devices are as shown in the following.
Remote output (RY) Y1000 is RYn0: Program number selection input (bit 0)
Remote register (RWr) W0 is RWrn: Monitor 1 data, lower 16 bits
Remote register (RWw) W100 is RWwn: Monitor 1
In the case of Remote input (RX): X1000, Station number of ABSODEX: 2 and Number of
stations occupied of station number 1: 1, X1010 corresponds to RXn0. In other words,
Set address of unit + Number of stations occupied before ABSODEX x 16
This value is the beginning address of ABSODEX.