CB FALCON MODBUS COMMUNICATION
19
Table 4. CB Falcon Modbus register map
ANNUNCIATION
CONFIGURATION
0130 0304 Annunciation enable R/W U16 0=Annunciation disabled,
1=Annunciation enabled
0131 0305 Annunciator mode R/W U16 0=Fixed,
1=Programmable
0132-013E 0306-0318 Annunciator 1 configuration R/W See table 6.
013F-014B 0319-0331 Annunciator 2 configuration R/W See table 6.
014C-0158 0332-0344 Annunciator 3 configuration R/W See table 6.
0159-0165 0345-0357 Annunciator 4 configuration R/W See table 6.
0166-0172 0358-0370 Annunciator 5 configuration R/W See table 6.
0173-017F 0371-0383 Annunciator 6 configuration R/W See table 6.
0180-018C 0384-0396 Annunciator 7 configuration R/W See table 6.
018D-0199 0397-0409 Annunciator 8 configuration R/W See table 6.
019A-01A5 0410-0421 PII configuration R/W See table 7.
01A6-01B1 0422-0433 LCI configuration R/W See table 7.
01B2-01BD 0434-0445 ILK configuration R/W See table 7.
01BE-01BF 0446-0447 RESERVED
DHW CONFIGURATION
01C0 0448 DHW enable R/W U16 0=DHW disabled,
1=DHW enabled
01C1 0449 DHW demand switch R/W U16 Source of DHW demand:
0= Modulation sensor only,
1=EnviraCOM DHW request,
2=DHW switch,
3=Unused,
4=STAT terminal,
5=Reserved,
6=Modbus STAT,
7=Auto: S6 or EnviraCOM DHW request,
8=Auto: S6 or sensor only,
9=Plate heat exchanger
01C2 0450 DHW priority vs CH R/W U16 0=CH > DHW,
1=DHW > CH
01C3 0451 DHW priority vs LL R/W U16 0=LL > DHW,
1=DHW > LL
01C4 0452 DHW priority time R/W U16 0=No DHW priority time,
>0=DHW priority time (seconds)
01C5 0453 DHW setpoint R/W U16
-40°-130° (0.1°C precision)
a
01C6 0454 DHW time of day setpoint R/W U16
-40°-130° (0.1°C precision)
a
Setpoint when Time Of Day
switch is on.
01C7 0455 DHW on hysteresis R/W U16
0°-130° (0.1°C precision)
a
01C8 0456 DHW off hysteresis R/W U16
0°-130° (0.1°C precision)
a
01C9 0457 DHW P-gain R/W U16 0-1000
01CA 0458 DHW I-gain R/W U16 0-1000
01CB 0459 DHW D-gain R/W U16 0-1000
01CC 0460 DHW hysteresis step time R/W U16 0-64800 seconds (0=Disable hysteresis stepping)
01CD 0461 DHW modulation sensor R/W U16 Sensor used for DHW modulation:
0=DHW sensor,
1=Outlet sensor,
2=Inlet sensor,
3=Modbus,
4=Auto: DHW or Inlet sensor,
5=Auto: DHW or Outlet sensor