EasyManua.ls Logo

CleaverBrooks CFC-E Series - Page 38

CleaverBrooks CFC-E Series
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BOILER BOOK CFC-E ENGINEERING DATA
38
Figure 30. Two Opening Engineered Method
E. Size the openings by using the formula:
Area in square feet = cfm/fpm
Where cfm = cubic feet per minute of air
Where fpm = feet per minute of air
2. Amount of Air Required (cfm).
A. Combustion Air = 0.25 cfm per kBtuh.
B. Ventilation Air = 0.05 cfm per kBtuh.
C. Total air = 0.3 cfm per kBtuh (up to 1000 feet elevation. Add 3% more per 1000 feet of
added elevation).
3. Acceptable air velocity in the Boiler Room (fpm).
A. From floor to 7 feet high = 250 fpm.
B. Above 7 feet above floor = 500 fpm.
Example: Determine the area of the boiler room air supply openings for (2) Clearfire 1800 boilers at
750 feet elevation. The air openings to be 5 feet above floor level.
Air required: 1800 x 2 = 3600 kBtuh. From 2C above, 3600 x 0.3 = 1,080 cfm.
Air Velocity: Up to 7 feet = 250 fpm from 3 above.
Area required: Area = cfm/fpm = 1,080/250 = 4.32 square feet total.
Area/Opening: 4.32/2 = 2.16 sq-ft/opening (2 required).
Consult local codes, which may supersede these requirements.

Related product manuals