What to do if there is a pilot flame but no main flame in my CleaverBrooks FLX Boiler?
A
Antonio HawkinsAug 23, 2025
If your CleaverBrooks Boiler shows a pilot flame but no main flame, first consider if the unit is gas-fired or oil-fired. For gas-fired units, check if the manual gas cock is closed, if the main gas valve is inoperative, or if the gas pressure regulator is malfunctioning. For oil-fired units, ensure the oil supply isn't cut off by an obstruction, closed valve, or loss of suction. Also, verify the supply pump is operational, there is sufficient fuel, the main oil valve is working, and the oil nozzle, gun, and lines are clear. Additionally, check the flame detector for defects, obstructions in the sight tube, or a dirty lens. Furthermore, verify sufficient voltage at the main fuel valve circuit terminal and ensure that the pilot flame is sufficient.
A
Alexander DanielAug 26, 2025
How to fix CleaverBrooks Boiler burner that does not start?
M
Mark NashAug 26, 2025
If the CleaverBrooks Boiler burner does not start, here are a few things to check:
* Ensure there is voltage at the program relay power input terminals by verifying the main disconnect switch is not open, the control circuit fuse is intact, and all electrical connections are secure.
* Reset the program relay safety switch, if necessary.
* Confirm the limit circuit is completed by checking pressure, temperature, and water levels.
* Verify fuel pressure is within the settings of the low and high-pressure switches, and inspect the burner air proving switch and high-fire limit switch.
* Investigate and repair any high or low gas pressure issues.
C
Cassandra HolmesSep 2, 2025
Why is the modulating motor not operating in my CleaverBrooks Boiler?
A
Anna JohnsonSep 2, 2025
If the modulating motor in your CleaverBrooks Boiler is not operating, here are some things to investigate:
* Ensure the manual-automatic switch is in the correct position.
* Check for any looseness or jamming in the linkage.
* If the motor does not drive to open or close during pre-purge or close on burner shutdown:
* Inspect the motor for defects.
* Check for loose electrical connections.
* Test the damper motor transformer for defects.
* If the motor does not operate on demand:
* Ensure the manual-automatic switch is in the correct position.
* Verify the modulating control is properly set and operative.
* Inspect the motor for defects.
* Check for loose electrical connections.
* Test the damper motor transformer for defects.
J
Jennifer HodgesSep 4, 2025
Why does my CleaverBrooks Boiler burner stay in low-fire?
M
mark69Sep 5, 2025
If the CleaverBrooks Boiler burner remains in low-fire, here’s what you should check:
* Verify if the pressure or temperature is above the modulating control setting.
* Confirm that the manual-automatic switch is in the correct position.
* Inspect the modulating motor for proper operation.
* Check the modulating control for any defects.
* Look for any binding or loose linkages, cams, setscrews, etc.
J
jacksontiffanySep 9, 2025
Why does my CleaverBrooks Boiler shut down during firing?
M
Michael SheltonSep 9, 2025
A CleaverBrooks Boiler shutting down during firing can stem from several issues. It could be due to a loss or stoppage of the fuel supply or a defective fuel valve with a loose electrical connection. The flame detector might be weak or defective, or the lens could be dirty, or the sight tube obstructed. Check the limit circuit for an opened safety control if the programmer lockout switch hasn't tripped. If the programmer lockout switch has tripped, investigate the cause. Inspect the fuel lines and valves. Check the flame detector. Look for an open circuit in the running interlock circuit. The flame failure light indicates ignition failure, main flame failure, inadequate flame signal, or an open control in the running interlock circuit.
J
Jill ThompsonSep 14, 2025
Why is there excessive rust on the tubes of my CleaverBrooks FLX Boiler?
C
Christopher HughesSep 14, 2025
Excessive rust on the tubes of your CleaverBrooks Boiler is often due to condensation of flue gases on cool tubes. Modify the system to ensure return temperatures are above 120°F, or install a blend pump to guarantee water entering the boiler exceeds 120°F. An open stack or condensate running down the stack or breeching can also contribute; consider offsetting, insulating, and draining the stack. Frequent cold starts can exacerbate the issue; try resetting the controls for less cycling.