Tranquility
®
20
(TS) Series
Models TSD/H/V 006 - 070
60Hz - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N06
Revised: June 5, 2020
Table of Contents
Model Nomenclature - General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 26
Electrical - Power & Low Voltage Wiring 27
Electrical - Low Voltage Wiring 28
Electrical - Thermostat Wiring 29
TS Blower Performance Data - (ECM Motor) -
Standard Unit - No Reheat 30
TS Blower Performance Data - Standard Unit -
No Reheat (PSC Motor) 31
TS Blower Performance Data - Units with
ClimaDry
®
(PSC Motor) 32
ECM Blower Control 33
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 35
Typical Wiring Diagram - Units with CXM Board
and PSC Fan Motor (Single Phase) 36
Typical Wiring Diagram - Units with DXM2 Board
and PSC Fan Motor (Three Phase) 37
Typical Wiring Diagram - Units with CXM Board,
ECM Fan Motor, and MPC (DDC) Controls
(Single Phase) 38
CXM Controls 39
DXM2 Controls 40
Safety Features - CXM and DXM2 Controls 45
ClimaDry
®
Modulating Reheat Option 47
Unit Starting and Operating Conditions 49
Piping System Cleaning and Flushing 50
Flushing/Purging Units with ClimaDry
®
51
Unit and System Checkout 52
Unit Start-Up Procedure 53
Unit Operating Conditions 55
Preventive Maintenance 60
Functional Troubleshooting 61
Performance Troubleshooting 62
Start-Up Log Sheet 63
Functional Troubleshooting 64

Other manuals for ClimateMaster Tranquility 20 Series

Questions and Answers

  • M
    Matthew LamAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Tranquility 20?
    • L
      Lauren LandryAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, 24VAC between R and C on CXM/DXM2, and the primary/secondary voltage on the transformer.
  • L
    Lisa VincentAug 21, 2025
    How do I troubleshoot Condensate Fault Code 6 on my ClimateMaster Heat Pump?
    • T
      Tammy WuAug 21, 2025
      If your ClimateMaster Heat Pump shows Condensate Fault Code 6, check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Verify the piping slope is away from the unit and check the slope of the unit toward the outlet. Ensure proper venting by checking the vent location. Also, check for moisture shorting to the air coil and replace the air filter. If there is restricted return air flow, find and eliminate the restriction, and increase the return duct and/or grille size.
  • D
    David AguilarAug 23, 2025
    What to do if my ClimateMaster Tranquility 20 Heat Pump shows HP Fault Code 2 High Pressure?
    • E
      Elizabeth SimmonsAug 23, 2025
      If your ClimateMaster Heat Pump displays a High Pressure fault (Code 2), the issue might stem from several causes. If cooling, check the pump or valve operation/setting and ensure proper water flow. Make sure the water temperature is within the specified range for cooling. If heating, inspect the air filter and clean or replace if dirty. Also, examine the fan motor operation for any airflow restrictions. Ensure the air coil is clean and that the external static pressure aligns with the blower table. Verify that the return air temperature is within the design parameters, and check superheat/subcooling against the typical operating condition table. Finally, check the switch continuity and operation, replacing if necessary.
  • E
    emily71Aug 26, 2025
    What causes LP/LOC Fault Code 3 Low Pressure / Loss of Charge in ClimateMaster Tranquility 20 Heat Pump?
    • T
      Thomas RogersAug 26, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it may be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • T
    Thomas WarrenAug 28, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Heat Pump?
    • J
      James GutierrezAug 28, 2025
      If your ClimateMaster Heat Pump displays an Over/Under Voltage fault (Code 7), check the power supply and 24VAC voltage, both before and during operation. Inspect the power supply wire size. Consider whether a hard start kit is needed for the compressor. Also, check the 24VAC and unit transformer tap for correct power supply voltage. This applies to both undervoltage and overvoltage scenarios.
  • M
    mooreerikaAug 30, 2025
    How to fix LT1 Fault Code 4 Water coil low temperature limit in ClimateMaster Tranquility 20 Heat Pump?
    • A
      Amy MckeeAug 30, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. If heating, check the pump operation or water valve operation/setting for reduced or no water flow. Ensure that the strainer or filter is not plugged, clean or replace if necessary. Also, check and adjust the water flow to the proper rate. If using antifreeze, check the antifreeze density with a hydrometer. If needed, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within the design parameters and check the temperature and impedance correlation per the chart.
  • A
    Ashley SmithSep 1, 2025
    What causes LT2 Fault Code 5 Air coil low temperature limit in ClimateMaster Tranquility 20?
    • J
      Jerome HernandezSep 1, 2025
      If your ClimateMaster Heat Pump displays an Air coil low temperature limit fault (LT2 Fault Code 5), check for a dirty air filter and clean or replace it if necessary. Verify the fan motor operation and airflow isn't restricted. Also, check the external static pressure against the blower table. If the air temperature is out of range, ensure that the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), note that normal airside applications will require 30°F [-1°C] only. Finally, check the temperature and impedance correlation per the chart.
  • A
    asalazarSep 3, 2025
    Why does my ClimateMaster Tranquility 20 Heat Pump unit short cycle?
    • A
      April PinedaSep 4, 2025
      If your ClimateMaster Heat Pump is short cycling, start by checking and cleaning the air filter. Also, ensure the unit isn't in 'test mode'; if it is, reset the power or wait 20 minutes for it to automatically exit. Check the sizing for the actual load of the space. Finally, check the compressor overload and replace if necessary.
  • M
    Michelle SmithSep 6, 2025
    Why does only the fan run on my ClimateMaster Heat Pump?
    • A
      Alicia AdamsSep 6, 2025
      If only the fan is running on your ClimateMaster Heat Pump, first ensure the thermostat is set for heating or cooling operation. Check for any lockout codes and reset the power. Inspect the compressor overload and replace if necessary. Finally, check the thermostat wiring at the heat pump, jumpering Y and R for compressor operation in test mode.
  • L
    lisastevensonSep 8, 2025
    What does Unit Performance Sentinel Code 8 mean for ClimateMaster Heat Pump?
    • S
      Selena RubioSep 8, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could indicate a few issues. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Unit Overview and Installation

Model Nomenclature and Configuration

Explains the unit's model designation system, size, revision level, and voltage configurations.

Installation Guidelines

Covers horizontal, vertical installation, piping, and system setup procedures.

Unit Checkout and Start-Up Procedures

Checklists for verifying unit and system installation before powering up and initial start-up.

System Applications, Water Quality, and Electrical

Application Types and Water Quality

Guidelines for water-loop, ground-loop, and ground-water systems, including water quality assessment.

Electrical Wiring and Control Systems

Instructions for power, low voltage, thermostat, and accessory wiring, plus control system operation.

Performance, Safety, and Troubleshooting

Blower Performance Data

Tables detailing blower performance for ECM and PSC motors under various conditions.

Safety Features and Fault Diagnosis

Explains safety features, fault conditions, and diagnostic indicators for controls.

Troubleshooting Guides

Guides for diagnosing and resolving functional and performance issues with the unit.

Operation Modes, Maintenance, and Support

Wiring Diagrams

Wiring diagrams for different control board and fan motor configurations.

ClimaDry Modulating Reheat Operation

Explains the operation and components of the ClimaDry® reheat system.

Preventive Maintenance

Routine maintenance procedures for key unit components.

Warranty Information

Details the limited express warranty terms for products.

ClimateMaster Tranquility 20 Series Specifications