A: STAND-ALONE IN MASTER MODE
• local monitoring
• one display
• Physical BAS control
B: LOCAL GROUP, MASTER
+ 1-9 SLAVES
• local monitoring (all units in the group)
• one display
• Physical BAS control (master)
C: OPERATED AND MONITORED
BY A BAS
• Local monitoring only for connected hood
• 1…n display if local monitoring needed
• Physical BAS Control (overrides ModBus)
• Control via ModBus
• Modbus master not supplied
Building automation (physical)
• alert
• permission to run
Building automation (physical)
• alert
• permission to run
Building automation (physical)
• alert
• permission to run
• needed for all units
Master mode
Master mode
ModBus master
(building automation)
All in slave mode
+ ModBus address
ModBus compatible cable
ModBus compatible cable
Slaves 1..9
CAT5, RJ45
CAT5, RJ45
A
B
C