7.14 Fire alarm: conguration
The unit is able to manage the signal coming from a re detection system or le control unit installed built-in, activating one of the logics
illustrated,which can be set by parameter.
Par 3029 TypeFireMode
In the presence of alarm signal, the compressors are Always switched o; moreover, the remote on-o is disabled together with the switch
on/o control from keypad.
The unit cannot be used as smoke extractor.
Any re detection devices built-in the unit must be considered as an auxiliary safety system, and, accordingly, must not be a replacement for
any re detection devices in the room.
7.15 Application for low outdoor temperature
Option indicated for very cold climates, where the outside temperature can be between -10 and – 30°C.
The option includes self-regulating heaters with thermostats that can protect the electrical panel from freezing to make sure it operates
correctly.
The accessory is also active with unit OFF; the unit must remain powered.
7.16 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
total voltages and absorptions with unit at full load
absorptions of the dierent electric loads (compressors, fans, pumps etc)
temperatures and ows of the dierent uids (water, air) both in input and in output from the unit
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
The measurements must be kept and made available during maintenance interventions.