Troubleshooting
Error
code
Malfunctioning
or protection
Cause of the problem and corrective action
L0
Compressor inverter module
fault.
Check:
1. compressor working pressures.
2. compressor winding heaters.
3. U V W sequence between inverter board and compressor.
4. L1 L2 L3 sequence between inverter board and filter board.
5. inverter board.
L1
Low voltage BUS protection
of the inverter module.
L2
High voltage BUS protection
of the inverter module.
L4 MCE protection.
L5 Speed 0 protection.
L7 Phase sequence error.
L8
Compressor frequency
variation greater than 15 Hz
in 1 sec.
L9
Compressor frequency
dierence to target greater
than 15 Hz.