IS-NT-Async-SPI, SW Version 1.2,   ©ComAp – February 2011                                
IS-NT-Async-SPI-1.2.PDF 
 
4
 
 
 
 
WARNING – VERY IMPORTANT !!! 
Be aware that the binary outputs can change state during and after software 
reprogramming (before the controller is used again ensure that the proper 
configuration and setpoint settings are set in the controller). 
 
Every time you want disconnect following InteliGen
NT
 controller terminals:  
 
•  Mains voltage measuring   
 
 
Switch the controller to MAN mode and disconnect the Binary outputs Starter and Fuel 
to avoid unexpected automatic start of gen-set and GCB closing. 
 
 
 
!!! CAUTION !!! 
Dangerous voltage 
The terminals for voltage and current measurement should never be touched. 
Properly connect the grounding terminals. 
Do not disconnect the CT terminals for any reason. 
Adjust set points 
All setpoints are preadjusted to their typical values. But the set points  in the “Basic settings” settings 
group !!must!! be adjusted before the first startup of the gen-set.  
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS  
CAN DESTROY THE GEN-SET !!! 
 
The following instructions are for qualified personnel only. To avoid personal injury do 
not perform any action not specified in this User guide !!!