IS-NT-Async-SPI, SW Version 1.2,   ©ComAp – February 2011                                
IS-NT-Async-SPI-1.2.PDF 
 
60
If you do not want to send active e-mails, you may leave this setpoint blank, as well as other setpoints 
related to SMTP server and e-mail settings.  
Proper setting of SMTP-related setpoints as well as controller mailbox are essential for sending alerts via e-
mails 
Contr mailbox    [ - ] 
Enter an existing e-mail address into this setpoint. This address will be used as sender address in active e-
mails that will be sent from the controller. Do not enter your or other recipient's e-mail address. Recipient's 
addresses are to be entered into the setpoints AcallCH1-Addr, AcallCH2-Addr and AcallCH3-Addr. 
Hint:
 
Most of SMTP server will reject sending e-mails that contain nonexisting address in the sender address field. 
Time zone      [ - ] 
This setpoint is used to select the time zone where the controller is located. See your computer time zone 
setting (click on the time indicator located in the rightmost position of the the windows task bar) if you are not 
sure about your time zone. 
Hint:
 
If the time zone is not selected properly the active e-mails may contain incorrect information about sending 
time, which may result in confusion when the respective problem actually occured.  
DNS IP      [ - ] 
In fixed settings mode this setpoint is used to adjust the domain name server (DNS), which is needed to 
traslate domain names in e-mail addresses and server names into correct IP addresses.  
In Automatic settings mode this setpoint is used to display DNS server, which has been assigned by the 
DHCP server.  
ECU Diag      [ DISABLED / ENABLED ]   (FV) 
When set to disabled, the ECU advanced diagnostics is disabled to allow the cooperation with external 
diagnostics tool. 
Alarm list indication “ECU Diag disabled” is indicated when ECU diagnostics is disabled. 
Force value possibility: Yes 
SHxOcol detect    [ DISABLED / ENABLED ] 
This setpoint is dedicated for virtual peripheries; it can enable / disable error messages when more then one 
master (source) is configured. 
Engine params  
Starting RPM      [ RPM ]   (FV) 
“Firing” speed when controller stops cranking. 
Step:     1            RPM 
Range:    0 – 1000 RPM 
Force value possibility: Yes 
 
Hint:
 
Under speed limit is given by Starting RPM value once the Under speed protection has been enabled. 
The Under speed protection becomes active 5s after reaching Starting RPM or other engine running 
condition regardless of the setting of Idle time (transition Idle -> Nominal RPM). 
Starting POil       [ bar ] (FV) 
Oil pressure limit for controller cranking termination = one of the engine running indications.  
To activate this function an Analog input must be configured to Analog logical input Oil press. 
Step:     0,1 bar 
Range:    0 – 10,0 bar 
Force value possibility: Yes