IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
This setpoint adjusts the maximum allowed negative difference between a 
particular cylinder temperature and average cylinder temperature at minimum 
power level adjusted by setpoint PminCylDifEval. This setpoint is one of four 
setpoints that define the allowed area of cylinder temperature differencies 
depending on gen-set power. See the setpoint Max+CylDifPmin for more details. 
 
Setpoint: Max+CylDifPnom 
This setpoint adjusts the maximum allowed positive difference between a 
particular cylinder temperature and average cylinder temperature at nominal 
power. This setpoint is one of four setpoints that define the allowed area of 
cylinder temperature differencies depending on gen-set power. See the setpoint 
Max+CylDifPmin for more details. 
 
Setpoint: Max-CylDifPnom 
This setpoint adjusts the maximum allowed negative difference between a 
particular cylinder temperature and average cylinder temperature at nominal 
power. This setpoint is one of four setpoints that define the allowed area of 
cylinder temperature differencies depending on gen-set power. See the setpoint 
Max+CylDifPmin for more details. 
 
Setpoint: PminCylDifEval 
This setpoint adjusts the gen-set power level below which the cylinder 
temperature difference protection is not evaluated. Learn more about this 
protection in the description of the setpoint Max+CylDifPmin. 
 
Setpoint: CylDifEvalDel 
This setpoint adjusts the evaluation delay of the cylinder temperature difference 
protection. Learn more about this protection in the description of the setpoint 
Max+CylDifPmin.