IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
152
Related FW
3.0
Description
This setpoint adjusts the maximum allowed negative difference between a
particular cylinder temperature and average cylinder temperature at minimum
power level adjusted by setpoint PminCylDifEval. This setpoint is one of four
setpoints that define the allowed area of cylinder temperature differencies
depending on gen-set power. See the setpoint Max+CylDifPmin for more details.
Setpoint: Max+CylDifPnom
Group
Engine protect
Range [units]
-32000 .. +32000 [°C]
Related FW
3.0
Description
This setpoint adjusts the maximum allowed positive difference between a
particular cylinder temperature and average cylinder temperature at nominal
power. This setpoint is one of four setpoints that define the allowed area of
cylinder temperature differencies depending on gen-set power. See the setpoint
Max+CylDifPmin for more details.
Setpoint: Max-CylDifPnom
Group
Engine protect
Range [units]
-32000 .. +32000 [°C]
Related FW
3.0
Description
This setpoint adjusts the maximum allowed negative difference between a
particular cylinder temperature and average cylinder temperature at nominal
power. This setpoint is one of four setpoints that define the allowed area of
cylinder temperature differencies depending on gen-set power. See the setpoint
Max+CylDifPmin for more details.
Setpoint: PminCylDifEval
Group
Engine protect
Range [units]
0.0 .. Nomin power [kW]
Related FW
3.0
Description
This setpoint adjusts the gen-set power level below which the cylinder
temperature difference protection is not evaluated. Learn more about this
protection in the description of the setpoint Max+CylDifPmin.
Setpoint: CylDifEvalDel
Group
Engine protect
Range [units]
0 .. 600 [s]
Related FW
3.0
Description
This setpoint adjusts the evaluation delay of the cylinder temperature difference
protection. Learn more about this protection in the description of the setpoint
Max+CylDifPmin.

Table of Contents

Other manuals for ComAp IG-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NTC-BB and is the answer not in the manual?

ComAp IG-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIG-NTC-BB
CategoryController
LanguageEnglish

Related product manuals