IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
 
Setpoint: ExtValue1 rate 
This setpoint adjusts the rate pre second at which the ExtValue 1 is beeing 
changed while the input ExtValue1 up or ExtValue1 down is active. 
 
Setpoint: ExtValue2deflt 
This setpoint adjusts the reset (initial) value of the ExtValue 2. This initial value is 
applied either when the controller is powered-on or when the ExtValue 2 is reset 
by the binary input ExtValue2reset. 
 
Setpoint: ExtValue2LoLim 
-32000 .. ExtValue2HiLim [X]  
This setpoint adjusts the low limit of the value of ExtValue 2 if the value is 
lowered/raised by the binary inputs ExtValue2 up and ExtValue2 down. The 
ExtValue 2 is never lowered below this limit. 
NOTE:  
This limit is not taken into account if the value ExtValue 2 is written remotely from 
a terminal using the appropriate command ExtValue #n.  
 
NOTE:  
For IS-NT only. 
 
 
Setpoint: ExtValue2HiLim