IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
by the optimalization function.  
 
Value: Act Reserve 
 
Value: Reserve 
Actual absolute reserve for start. This value contains a copy of the setpoint 
#LoadResStrt from the currently selected reserve set. 
 
Value: Reserve Stp 
Actual absolute reserve - when the reserve is higher than this value the last 
started gen-set (the gen-set with the highest priority) is stopped. This value 
contains the following: #LoadResStop plus Nominal power of the genset which is 
first to stop. #LoadResStop is used from the currently selected reserve set. 
 
Value: ActRes rel 
 
Value: Res rel 
Actual relative reserve for start. This value contains a copy of the setpoint 
#%LdResStrt from the currently selected reserve set. 
 
Value: ResStp rel