InteliLite Global Guide
183
Setpoint group Basic settings Related FW 1.9.0
Range [units] AMF / MRS [-]
Default value AMF Alternative config NO
Step [-]
Comm object 12157 Related applications AMF
Config level Advanced
Setpoint visibility Always
Description
Based on this setpoint is defined basic controller function.
AMF Normal AMF operation
MRS When MRS mode is selected the controller will not perform AMF functions anymore. MCB
button will be inactive and also mains measurement and protections will be disabled.
The controller will keep TEST mode and the gen-set in AUTO mode will be able to start by
REMOTE START/STOP (PAGE 536) binary input.
Operation Mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 1 .. 32 [-]
Default value 1 Alternative config NO
Step 1
Comm object 24537 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more IL controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note: When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Controller Address
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals