InteliLite Global Guide
197
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. Prestart Time [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 15774 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 567) is configured.
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE (PAGE 567) is activated before logical
binary output STARTER (PAGE 597).
Note: In case Choke Lead is longer than 8s (cranking fail pause), Choke Lead will be limited to 8s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.
Choke Lead
6 back to List of setpoints

Table of Contents