EasyManuals Logo

ComAp InteliLite MRS16 Global Guide

ComAp InteliLite MRS16
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #201 background imageLoading...
Page #201 background image
InteliLite Global Guide
201
Setpoint group Engine settings Related FW 1.9.0
Range [units] Minimal Stabilization Time (page 200) .. 300 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8313 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When the gen-set has been started and the idle timer has elapsed, the generator voltage and frequency must
get within limits within this period of time, otherwise an appropriate shutdown alarm (generator voltage and/or
frequency) is issued.
Image 8.6 Maximal Stabilization Time
Maximal Stabilization Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0,0 .. 300,0 [s]
Default value 5,0 s Alternative config YES
Step 0,1 s
Comm object 10023 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
Protection Hold Off
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals