InteliLite Global Guide
263
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 9281 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT08 (PAGE 611) is configured
Description
Shutdown or BOC threshold level for AIN PROT08 (PAGE 611).
Note: These setpoints are used only if LAI AIN PROT08 (PAGE 611) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 8 Sd
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9282 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT08 (PAGE 611) is configured
Description
Delay for AIN PROT08 (PAGE 611).
Note: These setpoints are used only if LAI AIN PROT08 (PAGE 611) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 8 Delay
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals