EasyManuals Logo

ComAp InteliLite MRS16 Global Guide

ComAp InteliLite MRS16
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #327 background imageLoading...
Page #327 background image
InteliLite Global Guide
327
Setpoint group Plug-In Modules Related FW 1.9.0
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24279 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot B.
Slot B
6 back to List of setpoints
Group: CU AIN Calibration
Subgroup: Analog Input 1
Setpoint group CU AIN Calibration Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
0 (number of decimal is
given by sensor curve)
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 8431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 1.
CU AIN1 Calibration
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals