Setpoint visibility Always
Description
Connection type:
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplitPhase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L2 Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3 Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph4Wire Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
Autodetect
High Leg Delta
or
L1 >=100V; L1 <=140V
L2 >=140V
L3 >=100V; L3 <=140V
3PH3Wire or 3Ph4Wire
or
L1 >=100V
L2 >=100V
L3 >=100V
SplPhL1L2 L1 >=100V

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals