Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 15199 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 499) is active.
ECU Speed Adjustment 3
6 back to List of setpoints
Group: CM-RS232-485
Setpoint group CM-RS232-485 Related FW 1.9.0
Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24522 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM1 channel.
Direct InteliConfig communication protocol via serial cable.
MODBUS MODBUS protocol.
DualSlave Dual operation protocol - slave function
DualMaster Dual operation protocol - master function
COM1 Mode
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals