InteliLite Global Guide
543
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1385
Description
The output is closed when there is the warning alarm from the analog input 4 of the controller present in the
alarmlist or isn’t confirmed.
AL AIN 4 Wrn
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1292
Description
This output is active when the Sd Battery Flat (page 673) or Wrn Battery < Voltage (page 655) alarm is
present in the alarmlist or isn’t confirm.
AL Battery Flat
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1272
Description
This output is active when the Battery Charger Fail (page 652) alarm is present in the alarmlist or isn’t
confirmed.
AL Battery Charger
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1995
Description
This output is active when the Wrn Battery > Voltage (page 655) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Overvoltage
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1994
Description
This output is active when the Wrn Battery < Voltage (page 655) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Undervoltage
6 back to Logical binary outputs alphabetically