InteliLite Global Guide
571
Related FW 1.9.0 Related applications AMF, MRS
Comm object 958
Description
Signal for starting and stopping of ECU.
ECU Run Stop
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 959
Description
This output is active when ECU Wait To Start Lamp is active.
ECU Wait To Start
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 349
Description
This output is active when the ECU sends an active “yellow lamp” flag, i.e. it has detected a non-critical
malfunction. This flag is taken from the DM1 frame on standard J1939 ECUs. Some ECUs provide this flag
in their own proprietary frames and some do not provide the flag at all.
ECU Yellow Lamp
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1250
Description
This is an output from the Exercise timer 1. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 1 (page 303) subgroup. This output is
active when Timer 1 is active.
Exercise Timer 1
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1251
Description
This is an output from the Exercise timer 2. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 2 (page 310) subgroup. This output is
active when Timer 2 is active.
Exercise Timer 2
6 back to Logical binary outputs alphabetically