InteliLite Global Guide
585
Related FW 1.9.0 Related applications AMF, MRS
Comm object 286
Description
Output has no function.
Not Used
6 back to Logical binary outputs alphabetically
LBO: P
Related FW 1.9.0 Related applications AMF, MRS
Comm object 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment of
the setpoints Power Switch On (page 223) and Power Switch Off (page 224). When the dummy load
function is used the switching ON of Power switch is block when the engine isn’t running and is allowed 30 s
after start of the engine.
Image 8.180 Power Switch
Note: Setpoints Power Switch On (page 223) and Power Switch Off (page 224) are invisible until
configuration of this LBO.
Power Switch
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 36
Description
Prestart